ENVIRONMENTAL CONSULTANTS LTD
Report No: AR/04/1662
Page 1 of 6
TYNEDALE HOUSE, AGED PERSONS HOME,
COWPEN, BLYTH, NORTHUMBERLAND
Survey to identify asbestos based materials
carried out on behalf of Northumberland County Council
Issue Date: 26 October 2004
Registered Office: Church Buildings, Station Road, Seaton Delaval,
Whitley Bay, TYNE & WEAR, NE25 0PT
Tel: (0191) 298 0198 Fax: (0191) 298 0199
Visit our Web-site at: http://www.vegaec.co.uk e-mail: xxxxx@xxxxxx.xx.xx
1634 278
Report No. AR/04/1662
Page No. 2 of 6
Contents
Page No
Introduction ---------------------------------------------------------------------------------------- 3
Asbestos Register --------------------------------------------------------------------------------- 4
Report Summary ---------------------------------------------------------------------------------- 5-6
Appendices
Appendix A – Survey Report Data Record Sheets
Appendix B – Material Algorithm
Appendix C – Bulk analysis and sample locations.
Procedure ASB/6 Appendix E, Page 1 of 1, Issue No.1, Issue Date 26/01/04, Issued by VEGA.
CONFIDENTIAL
ASBESTOS SURVEY REPORT
Page 3
of 6
INTRODUCTION
Report No: AR/04/1662
Date of Issue: 26/10/04
Client: Mr R Brown
Clients Order No: -
Northumberland County Council
County Hall
Date(s) of Survey: 13/10/04
Morpeth
Northumberland
Establishment Surveyed:
NE61 2EF
Tynedale House, Aged Persons Home,
Cowpen, Blyth, Northumberland
Area(s) Surveyed: All accessible areas.
Type of Survey: Type 2 - Standard Sampling, Identification and Assessment, (see Additional Information
section for definition)
Purpose, Aims and Objectives
This survey was undertaken to establish the presence and nature of asbestos based materials in the
area(s) surveyed. Surveying, sampling and assessment of asbestos-containing materials was
carried out in accordance with MDHS 100: July 2001.
Representative bulk and - if applicable - air samples were taken from the locations detailed in the
following pages of this report. The bulk samples were subject to a careful cleaning procedure
involving disintegration of the sample, acid washing, solvent washing, filtration etc., in order to
expose fibres in a form suitable for microscopic analysis. Analysis was carried out in accordance
with MDHS 77: June 1994 by documented in-house procedures.
Vega Environmental Consultants Ltd cannot accept responsibility for any errors or
misinterpretations introduced into a survey, or any resulting conclusions, as a result of a reduced
sampling frequency specified by a client.
This survey attempts to identify all asbestos materials within the agreed scope of work. However,
as asbestos materials can be completely hidden/buried within a structure, VEGA cannot accept
responsibility for additional materials that may be identified at a later date.
Analyst:________________
Authorised By: ________________
P Dean
E Brown (Technical Director)
Procedure ASB/6 APPENDIX A, Page 1 of 1, Issue No.8, Issue Date 26/01/04, Issued by VEGA
1634 278
ASBESTOS REGISTER – MATERIAL ASSESSMENT
Opinions and interpretations expressed herein are outside the scope of UKAS accreditation held by VEGA
Report No AR/04/1662
Page 4 of 6
Level of
Location of sample point/
Area Id
ID
Sample ID
Action
Description of suspect material
(P/SP/ID)
Ground Floor,
Laundry
Gas pipe – flange gasket
ID
BS/04
Ground Floor,
Boiler Room
Flange gaskets – various locations
SP
As BS/04
CODE
ACTION
Remove ASAP
Repair/Encapsulate ASAP
Leave Undisturbed and Monitor Situation
Procedure ASB/6 Appendix F, Page 1 of 1, Issue No. 1, Issue Date 26/01/04, Issued by VEGA.
CONFIDENTIAL
Page 5
of 6
Opinions and interpretations expressed herein are outside the scope of UKAS accreditation held by VEGA.
REPORT SUMMARY
Report No: AR/04/1662
Survey Specification:
Type 2 Survey:
Definition:
Type 2 Survey (Standard Sampling, Identification and Assessment): The analyst will
do a general walk around the whole area and look at all readily accessible areas. From his
experience the analyst will attempt to identify any asbestos and/or asbestos products
without the need for sampling. The areas will be assessed and where appropriate will be
presumed to contain asbestos. Where it appears highly likely that materials will contain
asbestos, there should be a
strong presumption that it does. All materials, which are
presumed to contain asbestos, must be assessed using the Material Assessment Algorithm.
Where practicable representative samples will be taken from all materials in accordance
with full sampling frequency recommendations and analysed. Sample points will be made
safe but redecoration will not be carried out. (see Appendix A)
On 13 October 2004, a type 2 survey was carried out at Tynedale House, Aged Persons
Home, Cowpen, Blyth, Northumberland. The premises surveyed were erected in 1984, a
single stoery construction with brick wals and a tiled pitched roof.
The purpose of the survey was to identify and report on the presence and condition of
asbestos based materials.
GROUND FLOOR
Laundry – flange gaskets to gas pipe is an
asbestos
containing
material
(ACM
sample BS/04). It is in good condition
and recommended it be left undisturbed
and monitored. Similar flange gaskets can
be found in the Boiler Room.
Level
Sample
Extent
Product
Condition
Surface
Asbestos
Score
Access
Action
of ID
ID
(m/m2/m3)
Type
(0,1,2,3)
Treatment
Type
(IA,OA,EA)
(A1,A2,A3)
(1,2,3)
(0,1,2,3)
(1,2,3)
ID
BS/04
<0.25m²
1
0
0
1
2
OA
A3
Procedure ASB/6 APPENDIX G, Page 1 of 1, Issue No. 1, Issue Date 26/01/04, Issued by VEGA
CONFIDENTIAL
Page 6
of 6
Opinions and interpretations expressed herein are outside the scope of UKAS accreditation held by VEGA.
Report No: AR/04/1662
DRAWING TO DEPICT ASBESTOS CONTAINING MATERIALS
AND ASBESTOS SAMPLE POINT LOCATIONS
MAIN BUILDING
Gas pipe flange
gasket
BS/04
Flange
gasket
as BS/04
Procedure ASB/6 APPENDIX H, Page 1 of 1, Issue No. 1, Issue Date 26/01/04, Issued by VEGA
VEGA ENVIRONMENTAL CONSULTANTS LTD
APPENDIX A
ASBESTOS SURVEY - DATA RECORD SHEET
Page 1
of 71
Opinions and interpretations expressed herein are outside the scope of UKAS accreditation held by VEGA
Report No: AR/04/1662
Contact: Mr R Brown
Date of survey: 13/10/04
Survey Type: 2
Client: Northumberland County
Analyst: P Dean and V Adlington
Council
Site Location: Tynedale House, Aged Persons Home,
Cowpen, Blyth, Northumberland
Area ID
Surveyed
Location of sample point /
Level of
Sample
Extent
Product Condition
Surface
Asbestos
Score
Access
Action
Yes/No
Description
ID
ID
(m/m2/m3)
Type
(0,1,2,3)
Treatment
Type
(IA,OA,EA)
(A1,A2,A3)
of suspect material
(P/SP/ID)
(1,2,3)
(0,1,2,3)
(1,2,3)
GROUND
FLOOR
Entrance Lobby
Yes
Ceiling – wood
SP
-
-
-
-
-
NA
-
-
-
Walls – glass and wood
SP
-
-
-
-
-
NA
-
-
-
Floor – carpet over concrete
SP
-
-
-
-
-
NA
-
-
-
Reception Area
Yes
Ceiling – wood and textured
ID
BS/01
-
-
-
-
NA
-
-
-
coating
Walls – plaster over brick
SP
-
-
-
-
-
NA
-
-
-
Floor – carpet over concrete
SP
-
-
-
-
-
NA
-
-
-
Level of ID: P – Presumed, SP – Strongly Presumed, ID – Identified.
Access: IA – Inaccessible, OA – Occasionally Accessed, EA – Easily/Regularly Accessed
Asbestos Type: NA – Non-Asbestos
Action: A1 – Remove ASAP, A2 – Repair/Encapsulate ASAP, A3 – Leave Undisturbed and Monitor Situation
Analyst – P Dean
Procedure ASB/6 APPENDIX B, Page 1 of 2, Issue No. 6, Issue Date 14/01/04, Issued by VEGA
VEGA ENVIRONMENTAL CONSULTANTS LTD
APPENDIX A
ASBESTOS SURVEY - DATA RECORD SHEET - continued
Page 2
of 71
Opinions and interpretations expressed herein are outside the scope of UKAS accreditation held by VEGA
Report No: AR/04/1662
Date of survey: 13/10/04
Area ID
Surveyed
Location of sample point /
Level of
Sample
Extent
Product Condition
Surface
Asbestos
Score
Access
Action
Yes/No
Description
ID
ID
(m/m2/m3)
Type
(0,1,2,3)
Treatment
Type
(IA,OA,EA)
(A1,A2,A3)
of suspect material
(P/SP/ID)
(1,2,3)
(0,1,2,3)
(1,2,3)
GROUND
FLOOR (cont)
Corridor 1
Yes
Ceiling – plasterboard
SP
-
-
-
-
-
NA
-
-
-
Walls – plaster over brick
SP
-
-
-
-
-
NA
-
-
-
Floor – carpet over concrete
SP
-
-
-
-
-
NA
-
-
-
Void above
Yes
Roof – internal loft insulation
ID
BS/02
-
-
-
-
NA
-
-
-
Walls – brick
SP
-
-
-
-
-
NA
-
-
-
Pipe insulation – MMMF
SP
-
-
-
-
-
NA
-
-
-
Loft insulation – MMMF
SP
-
-
-
-
-
NA
-
-
-
Level of ID: P – Presumed, SP – Strongly Presumed, ID – Identified.
Access: IA – Inaccessible, OA – Occasionally Accessed, EA – Easily/Regularly Accessed
Asbestos Type: NA – Non-Asbestos
Action: A1 – Remove ASAP, A2 – Repair/Encapsulate ASAP, A3 – Leave Undisturbed and Monitor Situation
Analyst – P Dean
Procedure ASB/6 APPENDIX B, Page 2 of 2, Issue No.5, Issue Date 23/01/03, Issued by VEGA
VEGA ENVIRONMENTAL CONSULTANTS LTD
APPENDIX A
ASBESTOS SURVEY - DATA RECORD SHEET - continued
Page 3
of 71
Opinions and interpretations expressed herein are outside the scope of UKAS accreditation held by VEGA
Report No: AR/04/1662
Date of survey: 13/10/04
Area ID
Surveyed
Location of sample point /
Level of
Sample
Extent
Product Condition
Surface
Asbestos
Score
Access
Action
Yes/No
Description
ID
ID
(m/m2/m3)
Type
(0,1,2,3)
Treatment
Type
(IA,OA,EA)
(A1,A2,A3)
of suspect material
(P/SP/ID)
(1,2,3)
(0,1,2,3)
(1,2,3)
GROUND
FLOOR (cont)
Office
Yes
Ceiling – plasterboard
SP
-
-
-
-
-
NA
-
-
-
Walls – plaster over brick
SP
-
-
-
-
-
NA
-
-
-
Floor – carpet over concrete
SP
-
-
-
-
-
NA
-
-
-
Staff Room
Yes
Ceiling – plasterboard
SP
-
-
-
-
-
NA
-
-
-
Walls – ceramic tiles over brick
SP
-
-
-
-
-
NA
-
-
-
Corner boxing
SP
-
-
-
-
-
NA
-
-
-
Fire blanket
SP
-
-
-
-
-
NA
-
-
-
Floor – vinyl over concrete
SP
-
-
-
-
-
NA
-
-
-
Level of ID: P – Presumed, SP – Strongly Presumed, ID – Identified.
Access: IA – Inaccessible, OA – Occasionally Accessed, EA – Easily/Regularly Accessed
Asbestos Type: NA – Non-Asbestos
Action: A1 – Remove ASAP, A2 – Repair/Encapsulate ASAP, A3 – Leave Undisturbed and Monitor Situation
Analyst – P Dean
Procedure ASB/6 APPENDIX B, Page 2 of 2, Issue No.5, Issue Date 23/01/03, Issued by VEGA
VEGA ENVIRONMENTAL CONSULTANTS LTD
APPENDIX A
ASBESTOS SURVEY - DATA RECORD SHEET - continued
Page 4
of 71
Opinions and interpretations expressed herein are outside the scope of UKAS accreditation held by VEGA
Report No: AR/04/1662
Date of survey: 13/10/04
Area ID
Surveyed
Location of sample point /
Level of
Sample
Extent
Product Condition
Surface
Asbestos
Score
Access
Action
Yes/No
Description
ID
ID
(m/m2/m3)
Type
(0,1,2,3)
Treatment
Type
(IA,OA,EA)
(A1,A2,A3)
of suspect material
(P/SP/ID)
(1,2,3)
(0,1,2,3)
(1,2,3)
GROUND
FLOOR (cont)
Void behind
Yes
Pipe insulation – foam
SP
-
-
-
-
-
NA
-
-
-
Boxing
Staff Toilet
Yes
Ceiling – plasterboard
SP
-
-
-
-
-
NA
-
-
-
Walls – ceramic tiles over brick
SP
-
-
-
-
-
NA
-
-
-
Toilet cistern
SP
-
-
-
-
-
NA
-
-
-
Corner boxing
SP
-
-
-
-
-
NA
-
-
-
Floor – vinyl over concrete
SP
-
-
-
-
-
NA
-
-
-
Void behind
Yes
Pipe insulation – foam
SP
-
-
-
-
-
NA
-
-
-
Boxing
Level of ID: P – Presumed, SP – Strongly Presumed, ID – Identified.
Access: IA – Inaccessible, OA – Occasionally Accessed, EA – Easily/Regularly Accessed
Asbestos Type: NA – Non-Asbestos
Action: A1 – Remove ASAP, A2 – Repair/Encapsulate ASAP, A3 – Leave Undisturbed and Monitor Situation
Analyst – P Dean
Procedure ASB/6 APPENDIX B, Page 2 of 2, Issue No.5, Issue Date 23/01/03, Issued by VEGA
VEGA ENVIRONMENTAL CONSULTANTS LTD
APPENDIX A
ASBESTOS SURVEY - DATA RECORD SHEET - continued
Page 5
of 71
Opinions and interpretations expressed herein are outside the scope of UKAS accreditation held by VEGA
Report No: AR/04/1662
Date of survey: 13/10/04
Area ID
Surveyed
Location of sample point /
Level of
Sample
Extent
Product Condition
Surface
Asbestos
Score
Access
Action
Yes/No
Description
ID
ID
(m/m2/m3)
Type
(0,1,2,3)
Treatment
Type
(IA,OA,EA)
(A1,A2,A3)
of suspect material
(P/SP/ID)
(1,2,3)
(0,1,2,3)
(1,2,3)
GROUND
FLOOR (cont)
Small Lounge
Yes
Ceiling – plasterboard
SP
-
-
-
-
-
NA
-
-
-
Walls – plaster over brick
SP
-
-
-
-
-
NA
-
-
-
Floor – carpet over concrete
SP
-
-
-
-
-
NA
-
-
-
Duty Room
Yes
Ceiling – plasterboard
SP
-
-
-
-
-
NA
-
-
-
Walls – plaster over brick
SP
-
-
-
-
-
NA
-
-
-
Floor – carpet over concrete
SP
-
-
-
-
-
NA
-
-
-
Duty Room
Yes
Ceiling – plasterboard
SP
-
-
-
-
-
NA
-
-
-
Toilet
Walls – ceramic tiles over brick
SP
-
-
-
-
-
NA
-
-
-
Level of ID: P – Presumed, SP – Strongly Presumed, ID – Identified.
Access: IA – Inaccessible, OA – Occasionally Accessed, EA – Easily/Regularly Accessed
Asbestos Type: NA – Non-Asbestos
Action: A1 – Remove ASAP, A2 – Repair/Encapsulate ASAP, A3 – Leave Undisturbed and Monitor Situation
Analyst – P Dean
Procedure ASB/6 APPENDIX B, Page 2 of 2, Issue No.5, Issue Date 23/01/03, Issued by VEGA
VEGA ENVIRONMENTAL CONSULTANTS LTD
APPENDIX A
ASBESTOS SURVEY - DATA RECORD SHEET - continued
Page 6
of 71
Opinions and interpretations expressed herein are outside the scope of UKAS accreditation held by VEGA
Report No: AR/04/1662
Date of survey: 13/10/04
Area ID
Surveyed
Location of sample point /
Level of
Sample
Extent
Product Condition
Surface
Asbestos
Score
Access
Action
Yes/No
Description
ID
ID
(m/m2/m3)
Type
(0,1,2,3)
Treatment
Type
(IA,OA,EA)
(A1,A2,A3)
of suspect material
(P/SP/ID)
(1,2,3)
(0,1,2,3)
(1,2,3)
GROUND
FLOOR (cont)
Duty Room
Yes
Toilet cistern
SP
-
-
-
-
-
NA
-
-
-
Toilet (cont)
Corner boxing
SP
-
-
-
-
-
NA
-
-
-
Floor – vinyl over concrete
SP
-
-
-
-
-
NA
-
-
-
Vegetable Store
Yes
Ceiling – plasterboard
SP
-
-
-
-
-
NA
-
-
-
Walls – plaster over brick
SP
-
-
-
-
-
NA
-
-
-
Electrical equipment
SP
-
-
-
-
-
NA
-
-
-
Floor – vinyl over concrete
ID
BS/03
-
-
-
-
NA
-
-
-
Level of ID: P – Presumed, SP – Strongly Presumed, ID – Identified.
Access: IA – Inaccessible, OA – Occasionally Accessed, EA – Easily/Regularly Accessed
Asbestos Type: NA – Non-Asbestos
Action: A1 – Remove ASAP, A2 – Repair/Encapsulate ASAP, A3 – Leave Undisturbed and Monitor Situation
Analyst – P Dean
Procedure ASB/6 APPENDIX B, Page 2 of 2, Issue No.5, Issue Date 23/01/03, Issued by VEGA
VEGA ENVIRONMENTAL CONSULTANTS LTD
APPENDIX A
ASBESTOS SURVEY - DATA RECORD SHEET - continued
Page 7
of 71
Opinions and interpretations expressed herein are outside the scope of UKAS accreditation held by VEGA
Report No: AR/04/1662
Date of survey: 13/10/04
Area ID
Surveyed
Location of sample point /
Level of
Sample
Extent
Product Condition
Surface
Asbestos
Score
Access
Action
Yes/No
Description
ID
ID
(m/m2/m3)
Type
(0,1,2,3)
Treatment
Type
(IA,OA,EA)
(A1,A2,A3)
of suspect material
(P/SP/ID)
(1,2,3)
(0,1,2,3)
(1,2,3)
GROUND
FLOOR (cont)
Linen Store
Yes
Ceiling – plasterboard
SP
-
-
-
-
-
NA
-
-
-
Walls – plaster over brick
SP
-
-
-
-
-
NA
-
-
-
Floor – vinyl over concrete
SP
As
-
-
-
-
NA
-
-
-
BS/03
Laundry
Yes
Ceiling – plasterboard
SP
-
-
-
-
-
NA
-
-
-
Walls – plaster over brick
SP
-
-
-
-
-
NA
-
-
-
Electrical equipment
SP
-
-
-
-
-
NA
-
-
-
Water boiler
SP
-
-
-
-
-
NA
-
-
-
Water boiler – flue pipe
SP
-
-
-
-
-
NA
-
-
-
Level of ID: P – Presumed, SP – Strongly Presumed, ID – Identified.
Access: IA – Inaccessible, OA – Occasionally Accessed, EA – Easily/Regularly Accessed
Asbestos Type: NA – Non-Asbestos
Action: A1 – Remove ASAP, A2 – Repair/Encapsulate ASAP, A3 – Leave Undisturbed and Monitor Situation
Analyst – P Dean
Procedure ASB/6 APPENDIX B, Page 2 of 2, Issue No.5, Issue Date 23/01/03, Issued by VEGA
VEGA ENVIRONMENTAL CONSULTANTS LTD
APPENDIX A
ASBESTOS SURVEY - DATA RECORD SHEET - continued
Page 8
of 71
Opinions and interpretations expressed herein are outside the scope of UKAS accreditation held by VEGA
Report No: AR/04/1662
Date of survey: 13/10/04
Area ID
Surveyed
Location of sample point /
Level of
Sample
Extent
Product Condition
Surface
Asbestos
Score
Access
Action
Yes/No
Description
ID
ID
(m/m2/m3)
Type
(0,1,2,3)
Treatment
Type
(IA,OA,EA)
(A1,A2,A3)
of suspect material
(P/SP/ID)
(1,2,3)
(0,1,2,3)
(1,2,3)
GROUND
FLOOR (cont)
Laundry (cont)
Yes
Gas pipe – flange gasket
ID
BS/04
<0.25m²
1
0
0
1
2
OA
A3
Floor – vinyl over concrete
SP
-
-
-
-
-
NA
-
-
-
Cleaner’s
Yes
Ceiling – plasterboard
SP
-
-
-
-
-
NA
-
-
-
Cupboard
Walls – plaster over brick
SP
-
-
-
-
-
NA
-
-
-
Electrical equipment
SP
-
-
-
-
-
NA
-
-
-
Floor – vinyl over concrete
SP
As
-
-
-
-
NA
-
-
-
BS/03
Level of ID: P – Presumed, SP – Strongly Presumed, ID – Identified.
Access: IA – Inaccessible, OA – Occasionally Accessed, EA – Easily/Regularly Accessed
Asbestos Type: NA – Non-Asbestos
Action: A1 – Remove ASAP, A2 – Repair/Encapsulate ASAP, A3 – Leave Undisturbed and Monitor Situation
Analyst – P Dean
Procedure ASB/6 APPENDIX B, Page 2 of 2, Issue No.5, Issue Date 23/01/03, Issued by VEGA
VEGA ENVIRONMENTAL CONSULTANTS LTD
APPENDIX A
ASBESTOS SURVEY - DATA RECORD SHEET - continued
Page 9
of 71
Opinions and interpretations expressed herein are outside the scope of UKAS accreditation held by VEGA
Report No: AR/04/1662
Date of survey: 13/10/04
Area ID
Surveyed
Location of sample point /
Level of
Sample
Extent
Product Condition
Surface
Asbestos
Score
Access
Action
Yes/No
Description
ID
ID
(m/m2/m3)
Type
(0,1,2,3)
Treatment
Type
(IA,OA,EA)
(A1,A2,A3)
of suspect material
(P/SP/ID)
(1,2,3)
(0,1,2,3)
(1,2,3)
GROUND
FLOOR (cont)
Food Store
Yes
Ceiling – plasterboard
SP
-
-
-
-
-
NA
-
-
-
Walls – plaster over brick
SP
-
-
-
-
-
NA
-
-
-
Electrical equipment
SP
-
-
-
-
-
NA
-
-
-
Floor – vinyl over concrete
SP
As
-
-
-
-
NA
-
-
-
BS/03
Entrance Lobby
Yes
Ceiling – plasterboard
SP
-
-
-
-
-
NA
-
-
-
2
Walls – plaster over brick
SP
-
-
-
-
-
NA
-
-
-
Electrical equipment
SP
-
-
-
-
-
NA
-
-
-
Floor – vinyl over concrete
SP
As
-
-
-
-
NA
-
-
-
BS/03
Level of ID: P – Presumed, SP – Strongly Presumed, ID – Identified.
Access: IA – Inaccessible, OA – Occasionally Accessed, EA – Easily/Regularly Accessed
Asbestos Type: NA – Non-Asbestos
Action: A1 – Remove ASAP, A2 – Repair/Encapsulate ASAP, A3 – Leave Undisturbed and Monitor Situation
Analyst – P Dean
Procedure ASB/6 APPENDIX B, Page 2 of 2, Issue No.5, Issue Date 23/01/03, Issued by VEGA
VEGA ENVIRONMENTAL CONSULTANTS LTD
APPENDIX A
ASBESTOS SURVEY - DATA RECORD SHEET - continued
Page 10
of 71
Opinions and interpretations expressed herein are outside the scope of UKAS accreditation held by VEGA
Report No: AR/04/1662
Date of survey: 13/10/04
Area ID
Surveyed
Location of sample point /
Level of
Sample
Extent
Product Condition
Surface
Asbestos
Score
Access
Action
Yes/No
Description
ID
ID
(m/m2/m3)
Type
(0,1,2,3)
Treatment
Type
(IA,OA,EA)
(A1,A2,A3)
of suspect material
(P/SP/ID)
(1,2,3)
(0,1,2,3)
(1,2,3)
GROUND
FLOOR (cont)
Tank Room
Yes
Ceiling – plasterboard
SP
-
-
-
-
-
NA
-
-
-
Boxing to beam – plasterboard
SP
-
-
-
-
-
NA
-
-
-
Walls – brick
SP
-
-
-
-
-
NA
-
-
-
Pipe insulation – foam
SP
-
-
-
-
-
NA
-
-
-
Water tank
SP
-
-
-
-
-
NA
-
-
-
Floor – concrete
SP
-
-
-
-
-
NA
-
-
-
Level of ID: P – Presumed, SP – Strongly Presumed, ID – Identified.
Access: IA – Inaccessible, OA – Occasionally Accessed, EA – Easily/Regularly Accessed
Asbestos Type: NA – Non-Asbestos
Action: A1 – Remove ASAP, A2 – Repair/Encapsulate ASAP, A3 – Leave Undisturbed and Monitor Situation
Analyst – P Dean
Procedure ASB/6 APPENDIX B, Page 2 of 2, Issue No.5, Issue Date 23/01/03, Issued by VEGA
VEGA ENVIRONMENTAL CONSULTANTS LTD
APPENDIX A
ASBESTOS SURVEY - DATA RECORD SHEET - continued
Page 11
of 71
Opinions and interpretations expressed herein are outside the scope of UKAS accreditation held by VEGA
Report No: AR/04/1662
Date of survey: 13/10/04
Area ID
Surveyed
Location of sample point /
Level of
Sample
Extent
Product Condition
Surface
Asbestos
Score
Access
Action
Yes/No
Description
ID
ID
(m/m2/m3)
Type
(0,1,2,3)
Treatment
Type
(IA,OA,EA)
(A1,A2,A3)
of suspect material
(P/SP/ID)
(1,2,3)
(0,1,2,3)
(1,2,3)
GROUND
FLOOR (cont)
Bin Store
Yes
Ceiling – plasterboard
SP
-
-
-
-
-
NA
-
-
-
Walls – brick
SP
-
-
-
-
-
NA
-
-
-
Pipe insulation – MMMF
SP
-
-
-
-
-
NA
-
-
-
Floor – concrete
SP
-
-
-
-
-
NA
-
-
-
Freezer Room
Yes
Ceiling – plasterboard
SP
-
-
-
-
-
NA
-
-
-
Walls – plaster over brick
SP
-
-
-
-
-
NA
-
-
-
Electrical equipment
SP
-
-
-
-
-
NA
-
-
-
Floor – vinyl over concrete
SP
As
-
-
-
-
NA
-
-
-
BS/03
Level of ID: P – Presumed, SP – Strongly Presumed, ID – Identified.
Access: IA – Inaccessible, OA – Occasionally Accessed, EA – Easily/Regularly Accessed
Asbestos Type: NA – Non-Asbestos
Action: A1 – Remove ASAP, A2 – Repair/Encapsulate ASAP, A3 – Leave Undisturbed and Monitor Situation
Analyst – P Dean
Procedure ASB/6 APPENDIX B, Page 2 of 2, Issue No.5, Issue Date 23/01/03, Issued by VEGA
VEGA ENVIRONMENTAL CONSULTANTS LTD
APPENDIX A
ASBESTOS SURVEY - DATA RECORD SHEET - continued
Page 12
of 71
Opinions and interpretations expressed herein are outside the scope of UKAS accreditation held by VEGA
Report No: AR/04/1662
Date of survey: 13/10/04
Area ID
Surveyed
Location of sample point /
Level of
Sample
Extent
Product Condition
Surface
Asbestos
Score
Access
Action
Yes/No
Description
ID
ID
(m/m2/m3)
Type
(0,1,2,3)
Treatment
Type
(IA,OA,EA)
(A1,A2,A3)
of suspect material
(P/SP/ID)
(1,2,3)
(0,1,2,3)
(1,2,3)
GROUND
FLOOR (cont)
Electricity
Yes
Ceiling – plasterboard
SP
-
-
-
-
-
NA
-
-
-
Room
Walls – plaster over brick and
SP
-
-
-
-
-
NA
-
-
-
fibreboard
Electrical equipment
SP
-
-
-
-
-
NA
-
-
-
Floor – vinyl over concrete
SP
As
-
-
-
-
NA
-
-
-
BS/03
Dining Room
Yes
Ceiling – plasterboard
SP
-
-
-
-
-
NA
-
-
-
Lobby
Walls – plaster over brick
SP
-
-
-
-
-
NA
-
-
-
Floor – carpet over concrete
SP
-
-
-
-
-
NA
-
-
-
Level of ID: P – Presumed, SP – Strongly Presumed, ID – Identified.
Access: IA – Inaccessible, OA – Occasionally Accessed, EA – Easily/Regularly Accessed
Asbestos Type: NA – Non-Asbestos
Action: A1 – Remove ASAP, A2 – Repair/Encapsulate ASAP, A3 – Leave Undisturbed and Monitor Situation
Analyst – P Dean
Procedure ASB/6 APPENDIX B, Page 2 of 2, Issue No.5, Issue Date 23/01/03, Issued by VEGA
VEGA ENVIRONMENTAL CONSULTANTS LTD
APPENDIX A
ASBESTOS SURVEY - DATA RECORD SHEET - continued
Page 13
of 71
Opinions and interpretations expressed herein are outside the scope of UKAS accreditation held by VEGA
Report No: AR/04/1662
Date of survey: 13/10/04
Area ID
Surveyed
Location of sample point /
Level of
Sample
Extent
Product Condition
Surface
Asbestos
Score
Access
Action
Yes/No
Description
ID
ID
(m/m2/m3)
Type
(0,1,2,3)
Treatment
Type
(IA,OA,EA)
(A1,A2,A3)
of suspect material
(P/SP/ID)
(1,2,3)
(0,1,2,3)
(1,2,3)
GROUND
FLOOR (cont)
Void above
Yes
Ceiling – plasterboard
SP
-
-
-
-
-
NA
-
-
-
Room adjacent
Corridor 1
Walls – plaster over brick
SP
-
-
-
-
-
NA
-
-
-
Floor – carpet over concrete
SP
-
-
-
-
-
NA
-
-
-
Corridor 2
Yes
Ceiling – plasterboard
SP
-
-
-
-
-
NA
-
-
-
Walls – plaster over brick
SP
-
-
-
-
-
NA
-
-
-
Floor – carpet over concrete
SP
-
-
-
-
-
NA
-
-
-
Level of ID: P – Presumed, SP – Strongly Presumed, ID – Identified.
Access: IA – Inaccessible, OA – Occasionally Accessed, EA – Easily/Regularly Accessed
Asbestos Type: NA – Non-Asbestos
Action: A1 – Remove ASAP, A2 – Repair/Encapsulate ASAP, A3 – Leave Undisturbed and Monitor Situation
Analyst – P Dean
Procedure ASB/6 APPENDIX B, Page 2 of 2, Issue No.5, Issue Date 23/01/03, Issued by VEGA
VEGA ENVIRONMENTAL CONSULTANTS LTD
APPENDIX A
ASBESTOS SURVEY - DATA RECORD SHEET - continued
Page 14
of 71
Opinions and interpretations expressed herein are outside the scope of UKAS accreditation held by VEGA
Report No: AR/04/1662
Date of survey: 13/10/04
Area ID
Surveyed
Location of sample point /
Level of
Sample
Extent
Product Condition
Surface
Asbestos
Score
Access
Action
Yes/No
Description
ID
ID
(m/m2/m3)
Type
(0,1,2,3)
Treatment
Type
(IA,OA,EA)
(A1,A2,A3)
of suspect material
(P/SP/ID)
(1,2,3)
(0,1,2,3)
(1,2,3)
GROUND
FLOOR (cont)
Void above
Yes
Roof – internal loft insulation
SP
As
-
-
-
-
NA
-
-
-
BS/02
Walls – brick
SP
-
-
-
-
-
NA
-
-
-
Pipe insulation – MMMF
SP
-
-
-
-
-
NA
-
-
-
Loft insulation – MMMF
SP
-
-
-
-
-
NA
-
-
-
Water tank insulation –
SP
-
-
-
-
-
NA
-
-
-
polystyrene
Corridor 2
Yes
Ceiling – plasterboard
SP
-
-
-
-
-
NA
-
-
-
Toilet 1
Walls – ceramic tiles over brick
SP
-
-
-
-
-
NA
-
-
-
Toilet cistern
SP
-
-
-
-
-
NA
-
-
-
Level of ID: P – Presumed, SP – Strongly Presumed, ID – Identified.
Access: IA – Inaccessible, OA – Occasionally Accessed, EA – Easily/Regularly Accessed
Asbestos Type: NA – Non-Asbestos
Action: A1 – Remove ASAP, A2 – Repair/Encapsulate ASAP, A3 – Leave Undisturbed and Monitor Situation
Analyst – P Dean
Procedure ASB/6 APPENDIX B, Page 2 of 2, Issue No.5, Issue Date 23/01/03, Issued by VEGA
VEGA ENVIRONMENTAL CONSULTANTS LTD
APPENDIX A
ASBESTOS SURVEY - DATA RECORD SHEET - continued
Page 15
of 71
Opinions and interpretations expressed herein are outside the scope of UKAS accreditation held by VEGA
Report No: AR/04/1662
Date of survey: 13/10/04
Area ID
Surveyed
Location of sample point /
Level of
Sample
Extent
Product Condition
Surface
Asbestos
Score
Access
Action
Yes/No
Description
ID
ID
(m/m2/m3)
Type
(0,1,2,3)
Treatment
Type
(IA,OA,EA)
(A1,A2,A3)
of suspect material
(P/SP/ID)
(1,2,3)
(0,1,2,3)
(1,2,3)
GROUND
FLOOR (cont)
Corridor 2
Yes
Corner boxing
SP
-
-
-
-
-
NA
-
-
-
Toilet 1 (cont)
Floor – vinyl over concrete
SP
-
-
-
-
-
NA
-
-
-
Tank Room 2
Yes
Ceiling – plasterboard
SP
-
-
-
-
-
NA
-
-
-
Walls – plaster over brick
SP
-
-
-
-
-
NA
-
-
-
Pipe insulation – MMMF
SP
-
-
-
-
-
NA
-
-
-
Hot water tank insulation –
SP
-
-
-
-
-
NA
-
-
-
MMMF
Floor – vinyl over concrete
SP
As
-
-
-
-
NA
-
-
-
BS/03
Level of ID: P – Presumed, SP – Strongly Presumed, ID – Identified.
Access: IA – Inaccessible, OA – Occasionally Accessed, EA – Easily/Regularly Accessed
Asbestos Type: NA – Non-Asbestos
Action: A1 – Remove ASAP, A2 – Repair/Encapsulate ASAP, A3 – Leave Undisturbed and Monitor Situation
Analyst – P Dean
Procedure ASB/6 APPENDIX B, Page 2 of 2, Issue No.5, Issue Date 23/01/03, Issued by VEGA
VEGA ENVIRONMENTAL CONSULTANTS LTD
APPENDIX A
ASBESTOS SURVEY - DATA RECORD SHEET - continued
Page 16
of 71
Opinions and interpretations expressed herein are outside the scope of UKAS accreditation held by VEGA
Report No: AR/04/1662
Date of survey: 13/10/04
Area ID
Surveyed
Location of sample point /
Level of
Sample
Extent
Product Condition
Surface
Asbestos
Score
Access
Action
Yes/No
Description
ID
ID
(m/m2/m3)
Type
(0,1,2,3)
Treatment
Type
(IA,OA,EA)
(A1,A2,A3)
of suspect material
(P/SP/ID)
(1,2,3)
(0,1,2,3)
(1,2,3)
GROUND
FLOOR (cont)
Dining Room 1
Yes
Ceiling – textured coating
ID
BS/05
-
-
-
-
NA
-
-
-
Walls – plaster over brick
SP
-
-
-
-
-
NA
-
-
-
Floor – carpet over concrete
SP
-
-
-
-
-
NA
-
-
-
Sluice Room
Yes
Ceiling – plasterboard
SP
-
-
-
-
-
NA
-
-
-
Walls – plaster over brick
SP
-
-
-
-
-
NA
-
-
-
Toilet cisterns
SP
-
-
-
-
-
NA
-
-
-
Floor – vinyl over concrete
SP
-
-
-
-
-
NA
-
-
-
Level of ID: P – Presumed, SP – Strongly Presumed, ID – Identified.
Access: IA – Inaccessible, OA – Occasionally Accessed, EA – Easily/Regularly Accessed
Asbestos Type: NA – Non-Asbestos
Action: A1 – Remove ASAP, A2 – Repair/Encapsulate ASAP, A3 – Leave Undisturbed and Monitor Situation
Analyst – P Dean
Procedure ASB/6 APPENDIX B, Page 2 of 2, Issue No.5, Issue Date 23/01/03, Issued by VEGA
VEGA ENVIRONMENTAL CONSULTANTS LTD
APPENDIX A
ASBESTOS SURVEY - DATA RECORD SHEET - continued
Page 17
of 71
Opinions and interpretations expressed herein are outside the scope of UKAS accreditation held by VEGA
Report No: AR/04/1662
Date of survey: 13/10/04
Area ID
Surveyed
Location of sample point /
Level of
Sample
Extent
Product Condition
Surface
Asbestos
Score
Access
Action
Yes/No
Description
ID
ID
(m/m2/m3)
Type
(0,1,2,3)
Treatment
Type
(IA,OA,EA)
(A1,A2,A3)
of suspect material
(P/SP/ID)
(1,2,3)
(0,1,2,3)
(1,2,3)
GROUND
FLOOR (cont)
First Aid Point
Yes
Ceiling – plasterboard
SP
-
-
-
-
-
NA
-
-
-
Walls – plaster over brick
SP
-
-
-
-
-
NA
-
-
-
Electrical equipment
SP
-
-
-
-
-
NA
-
-
-
Floor – vinyl over concrete
SP
As
-
-
-
-
NA
-
-
-
BS/03
Store 1
Yes
Ceiling – plasterboard
SP
-
-
-
-
-
NA
-
-
-
Walls – plaster over brick
SP
-
-
-
-
-
NA
-
-
-
Electrical equipment
SP
-
-
-
-
-
NA
-
-
-
Floor – vinyl over concrete
SP
As
-
-
-
-
NA
-
-
-
BS/03
Level of ID: P – Presumed, SP – Strongly Presumed, ID – Identified.
Access: IA – Inaccessible, OA – Occasionally Accessed, EA – Easily/Regularly Accessed
Asbestos Type: NA – Non-Asbestos
Action: A1 – Remove ASAP, A2 – Repair/Encapsulate ASAP, A3 – Leave Undisturbed and Monitor Situation
Analyst – P Dean
Procedure ASB/6 APPENDIX B, Page 2 of 2, Issue No.5, Issue Date 23/01/03, Issued by VEGA
VEGA ENVIRONMENTAL CONSULTANTS LTD
APPENDIX A
ASBESTOS SURVEY - DATA RECORD SHEET - continued
Page 18
of 71
Opinions and interpretations expressed herein are outside the scope of UKAS accreditation held by VEGA
Report No: AR/04/1662
Date of survey: 13/10/04
Area ID
Surveyed
Location of sample point /
Level of
Sample
Extent
Product Condition
Surface
Asbestos
Score
Access
Action
Yes/No
Description
ID
ID
(m/m2/m3)
Type
(0,1,2,3)
Treatment
Type
(IA,OA,EA)
(A1,A2,A3)
of suspect material
(P/SP/ID)
(1,2,3)
(0,1,2,3)
(1,2,3)
GROUND
FLOOR (cont)
Kitchen 1
Yes
Ceiling – plasterboard
SP
-
-
-
-
-
NA
-
-
-
High level ceiling heater
SP
-
-
-
-
-
NA
-
-
-
Walls – ceramic tiles over brick
SP
-
-
-
-
-
NA
-
-
-
Door – window strip
ID
BS/06
-
-
-
-
NA
-
-
-
Hand basin – wood panel below
SP
-
-
-
-
-
NA
-
-
-
Floor – vinyl over concrete
SP
-
-
-
-
-
NA
-
-
-
Void behind
Yes
No suspect material identified
-
-
-
-
-
-
-
-
-
-
Basin Panel
Level of ID: P – Presumed, SP – Strongly Presumed, ID – Identified.
Access: IA – Inaccessible, OA – Occasionally Accessed, EA – Easily/Regularly Accessed
Asbestos Type: NA – Non-Asbestos
Action: A1 – Remove ASAP, A2 – Repair/Encapsulate ASAP, A3 – Leave Undisturbed and Monitor Situation
Analyst – P Dean
Procedure ASB/6 APPENDIX B, Page 2 of 2, Issue No.5, Issue Date 23/01/03, Issued by VEGA
VEGA ENVIRONMENTAL CONSULTANTS LTD
APPENDIX A
ASBESTOS SURVEY - DATA RECORD SHEET - continued
Page 19
of 71
Opinions and interpretations expressed herein are outside the scope of UKAS accreditation held by VEGA
Report No: AR/04/1662
Date of survey: 13/10/04
Area ID
Surveyed
Location of sample point /
Level of
Sample
Extent
Product Condition
Surface
Asbestos
Score
Access
Action
Yes/No
Description
ID
ID
(m/m2/m3)
Type
(0,1,2,3)
Treatment
Type
(IA,OA,EA)
(A1,A2,A3)
of suspect material
(P/SP/ID)
(1,2,3)
(0,1,2,3)
(1,2,3)
GROUND
FLOOR (cont)
Bedroom 1
Yes
Ceiling – plasterboard
SP
-
-
-
-
-
NA
-
-
-
Walls – plaster over brick
SP
-
-
-
-
-
NA
-
-
-
Floor – carpet over concrete
SP
-
-
-
-
-
NA
-
-
-
Bedroom 2
Yes
Ceiling – plasterboard
SP
-
-
-
-
-
NA
-
-
-
Walls – plaster over brick
SP
-
-
-
-
-
NA
-
-
-
Floor – carpet over concrete
SP
-
-
-
-
-
NA
-
-
-
Bedroom 3
Yes
Ceiling – plasterboard
SP
-
-
-
-
-
NA
-
-
-
Walls – plaster over brick
SP
-
-
-
-
-
NA
-
-
-
Floor – carpet over concrete
SP
-
-
-
-
-
NA
-
-
-
Level of ID: P – Presumed, SP – Strongly Presumed, ID – Identified.
Access: IA – Inaccessible, OA – Occasionally Accessed, EA – Easily/Regularly Accessed
Asbestos Type: NA – Non-Asbestos
Action: A1 – Remove ASAP, A2 – Repair/Encapsulate ASAP, A3 – Leave Undisturbed and Monitor Situation
Analyst – P Dean
Procedure ASB/6 APPENDIX B, Page 2 of 2, Issue No.5, Issue Date 23/01/03, Issued by VEGA
VEGA ENVIRONMENTAL CONSULTANTS LTD
APPENDIX A
ASBESTOS SURVEY - DATA RECORD SHEET - continued
Page 20
of 71
Opinions and interpretations expressed herein are outside the scope of UKAS accreditation held by VEGA
Report No: AR/04/1662
Date of survey: 13/10/04
Area ID
Surveyed
Location of sample point /
Level of
Sample
Extent
Product Condition
Surface
Asbestos
Score
Access
Action
Yes/No
Description
ID
ID
(m/m2/m3)
Type
(0,1,2,3)
Treatment
Type
(IA,OA,EA)
(A1,A2,A3)
of suspect material
(P/SP/ID)
(1,2,3)
(0,1,2,3)
(1,2,3)
GROUND
FLOOR (cont)
Bedroom 4
Yes
Ceiling – plasterboard
SP
-
-
-
-
-
NA
-
-
-
Walls – plaster over brick
SP
-
-
-
-
-
NA
-
-
-
Floor – carpet over concrete
SP
-
-
-
-
-
NA
-
-
-
Bedroom 5
Yes
Ceiling – plasterboard
SP
-
-
-
-
-
NA
-
-
-
Walls – plaster over brick
SP
-
-
-
-
-
NA
-
-
-
Floor – carpet over concrete
SP
-
-
-
-
-
NA
-
-
-
Bedroom 6
Yes
Ceiling – plasterboard
SP
-
-
-
-
-
NA
-
-
-
Walls – plaster over brick
SP
-
-
-
-
-
NA
-
-
-
Floor – carpet over concrete
SP
-
-
-
-
-
NA
-
-
-
Level of ID: P – Presumed, SP – Strongly Presumed, ID – Identified.
Access: IA – Inaccessible, OA – Occasionally Accessed, EA – Easily/Regularly Accessed
Asbestos Type: NA – Non-Asbestos
Action: A1 – Remove ASAP, A2 – Repair/Encapsulate ASAP, A3 – Leave Undisturbed and Monitor Situation
Analyst – P Dean
Procedure ASB/6 APPENDIX B, Page 2 of 2, Issue No.5, Issue Date 23/01/03, Issued by VEGA
VEGA ENVIRONMENTAL CONSULTANTS LTD
APPENDIX A
ASBESTOS SURVEY - DATA RECORD SHEET - continued
Page 21
of 71
Opinions and interpretations expressed herein are outside the scope of UKAS accreditation held by VEGA
Report No: AR/04/1662
Date of survey: 13/10/04
Area ID
Surveyed
Location of sample point /
Level of
Sample
Extent
Product Condition
Surface
Asbestos
Score
Access
Action
Yes/No
Description
ID
ID
(m/m2/m3)
Type
(0,1,2,3)
Treatment
Type
(IA,OA,EA)
(A1,A2,A3)
of suspect material
(P/SP/ID)
(1,2,3)
(0,1,2,3)
(1,2,3)
GROUND
FLOOR (cont)
Bedroom 7
Yes
Ceiling – plasterboard
SP
-
-
-
-
-
NA
-
-
-
Walls – plaster over brick
SP
-
-
-
-
-
NA
-
-
-
Floor – carpet over concrete
SP
-
-
-
-
-
NA
-
-
-
Bedroom 8
Yes
Ceiling – plasterboard
SP
-
-
-
-
-
NA
-
-
-
Walls – plaster over brick
SP
-
-
-
-
-
NA
-
-
-
Floor – carpet over concrete
SP
-
-
-
-
-
NA
-
-
-
Level of ID: P – Presumed, SP – Strongly Presumed, ID – Identified.
Access: IA – Inaccessible, OA – Occasionally Accessed, EA – Easily/Regularly Accessed
Asbestos Type: NA – Non-Asbestos
Action: A1 – Remove ASAP, A2 – Repair/Encapsulate ASAP, A3 – Leave Undisturbed and Monitor Situation
Analyst – P Dean
Procedure ASB/6 APPENDIX B, Page 2 of 2, Issue No.5, Issue Date 23/01/03, Issued by VEGA
VEGA ENVIRONMENTAL CONSULTANTS LTD
APPENDIX A
ASBESTOS SURVEY - DATA RECORD SHEET - continued
Page 22
of 71
Opinions and interpretations expressed herein are outside the scope of UKAS accreditation held by VEGA
Report No: AR/04/1662
Date of survey: 13/10/04
Area ID
Surveyed
Location of sample point /
Level of
Sample
Extent
Product Condition
Surface
Asbestos
Score
Access
Action
Yes/No
Description
ID
ID
(m/m2/m3)
Type
(0,1,2,3)
Treatment
Type
(IA,OA,EA)
(A1,A2,A3)
of suspect material
(P/SP/ID)
(1,2,3)
(0,1,2,3)
(1,2,3)
GROUND
FLOOR (cont)
Bathroom 1
Yes
Ceiling – plasterboard
SP
-
-
-
-
-
NA
-
-
-
Walls – ceramic tiles over brick
SP
-
-
-
-
-
NA
-
-
-
Corner and low level boxing
SP
-
-
-
-
-
NA
-
-
-
Floor – vinyl over concrete
SP
-
-
-
-
-
NA
-
-
-
Lounge 1
Yes
Ceiling – plasterboard
SP
-
-
-
-
-
NA
-
-
-
Walls – plaster over brick
SP
-
-
-
-
-
NA
-
-
-
Floor – carpet over concrete
SP
-
-
-
-
-
NA
-
-
-
Level of ID: P – Presumed, SP – Strongly Presumed, ID – Identified.
Access: IA – Inaccessible, OA – Occasionally Accessed, EA – Easily/Regularly Accessed
Asbestos Type: NA – Non-Asbestos
Action: A1 – Remove ASAP, A2 – Repair/Encapsulate ASAP, A3 – Leave Undisturbed and Monitor Situation
Analyst – P Dean
Procedure ASB/6 APPENDIX B, Page 2 of 2, Issue No.5, Issue Date 23/01/03, Issued by VEGA
VEGA ENVIRONMENTAL CONSULTANTS LTD
APPENDIX A
ASBESTOS SURVEY - DATA RECORD SHEET - continued
Page 23
of 71
Opinions and interpretations expressed herein are outside the scope of UKAS accreditation held by VEGA
Report No: AR/04/1662
Date of survey: 13/10/04
Area ID
Surveyed
Location of sample point /
Level of
Sample
Extent
Product Condition
Surface
Asbestos
Score
Access
Action
Yes/No
Description
ID
ID
(m/m2/m3)
Type
(0,1,2,3)
Treatment
Type
(IA,OA,EA)
(A1,A2,A3)
of suspect material
(P/SP/ID)
(1,2,3)
(0,1,2,3)
(1,2,3)
GROUND
FLOOR (cont)
Void above
Yes
Roof – internal loft insulation
SP
As
-
-
-
-
NA
-
-
-
Rooms adjacent
BS/02
Corridor 2
Walls – brick
SP
-
-
-
-
-
NA
-
-
-
Pipe insulation – MMMF
SP
-
-
-
-
-
NA
-
-
-
Loft insulation – MMMF
SP
-
-
-
-
-
NA
-
-
-
Water tank insulation –
SP
-
-
-
-
-
NA
-
-
-
polystyrene
Level of ID: P – Presumed, SP – Strongly Presumed, ID – Identified.
Access: IA – Inaccessible, OA – Occasionally Accessed, EA – Easily/Regularly Accessed
Asbestos Type: NA – Non-Asbestos
Action: A1 – Remove ASAP, A2 – Repair/Encapsulate ASAP, A3 – Leave Undisturbed and Monitor Situation
Analyst – P Dean
Procedure ASB/6 APPENDIX B, Page 2 of 2, Issue No.5, Issue Date 23/01/03, Issued by VEGA
VEGA ENVIRONMENTAL CONSULTANTS LTD
APPENDIX A
ASBESTOS SURVEY - DATA RECORD SHEET - continued
Page 24
of 71
Opinions and interpretations expressed herein are outside the scope of UKAS accreditation held by VEGA
Report No: AR/04/1662
Date of survey: 13/10/04
Area ID
Surveyed
Location of sample point /
Level of
Sample
Extent
Product Condition
Surface
Asbestos
Score
Access
Action
Yes/No
Description
ID
ID
(m/m2/m3)
Type
(0,1,2,3)
Treatment
Type
(IA,OA,EA)
(A1,A2,A3)
of suspect material
(P/SP/ID)
(1,2,3)
(0,1,2,3)
(1,2,3)
GROUND
FLOOR (cont)
Corridor 3
Yes
Ceiling – plasterboard
SP
-
-
-
-
-
NA
-
-
-
Walls – plaster over brick
SP
-
-
-
-
-
NA
-
-
-
Floor – carpet over concrete
SP
-
-
-
-
-
NA
-
-
-
Void above
Yes
Roof – internal loft insulation
SP
As
-
-
-
-
NA
-
-
-
BS/02
Walls – brick
SP
-
-
-
-
-
NA
-
-
-
Pipe insulation – MMMF
SP
-
-
-
-
-
NA
-
-
-
Loft insulation – MMMF
SP
-
-
-
-
-
NA
-
-
-
Water tank insulation –
SP
-
-
-
-
-
NA
-
-
-
polystyrene
Level of ID: P – Presumed, SP – Strongly Presumed, ID – Identified.
Access: IA – Inaccessible, OA – Occasionally Accessed, EA – Easily/Regularly Accessed
Asbestos Type: NA – Non-Asbestos
Action: A1 – Remove ASAP, A2 – Repair/Encapsulate ASAP, A3 – Leave Undisturbed and Monitor Situation
Analyst – P Dean
Procedure ASB/6 APPENDIX B, Page 2 of 2, Issue No.5, Issue Date 23/01/03, Issued by VEGA
VEGA ENVIRONMENTAL CONSULTANTS LTD
APPENDIX A
ASBESTOS SURVEY - DATA RECORD SHEET - continued
Page 25
of 71
Opinions and interpretations expressed herein are outside the scope of UKAS accreditation held by VEGA
Report No: AR/04/1662
Date of survey: 13/10/04
Area ID
Surveyed
Location of sample point /
Level of
Sample
Extent
Product Condition
Surface
Asbestos
Score
Access
Action
Yes/No
Description
ID
ID
(m/m2/m3)
Type
(0,1,2,3)
Treatment
Type
(IA,OA,EA)
(A1,A2,A3)
of suspect material
(P/SP/ID)
(1,2,3)
(0,1,2,3)
(1,2,3)
GROUND
FLOOR (cont)
Dining Room 2
Yes
Ceiling – textured coating
SP
As
-
-
-
-
NA
-
-
-
BS/05
Walls – plaster over brick
SP
-
-
-
-
-
NA
-
-
-
Floor – carpet over concrete
SP
-
-
-
-
-
NA
-
-
-
Toilet 4
Yes
Ceiling – plasterboard
SP
-
-
-
-
-
NA
-
-
-
Walls – ceramic tiles over brick
SP
-
-
-
-
-
NA
-
-
-
Toilet cistern
SP
-
-
-
-
-
NA
-
-
-
Corner boxing
SP
-
-
-
-
-
NA
-
-
-
Floor – vinyl over concrete
SP
-
-
-
-
-
NA
-
-
-
Level of ID: P – Presumed, SP – Strongly Presumed, ID – Identified.
Access: IA – Inaccessible, OA – Occasionally Accessed, EA – Easily/Regularly Accessed
Asbestos Type: NA – Non-Asbestos
Action: A1 – Remove ASAP, A2 – Repair/Encapsulate ASAP, A3 – Leave Undisturbed and Monitor Situation
Analyst – P Dean
Procedure ASB/6 APPENDIX B, Page 2 of 2, Issue No.5, Issue Date 23/01/03, Issued by VEGA
VEGA ENVIRONMENTAL CONSULTANTS LTD
APPENDIX A
ASBESTOS SURVEY - DATA RECORD SHEET - continued
Page 26
of 71
Opinions and interpretations expressed herein are outside the scope of UKAS accreditation held by VEGA
Report No: AR/04/1662
Date of survey: 13/10/04
Area ID
Surveyed
Location of sample point /
Level of
Sample
Extent
Product Condition
Surface
Asbestos
Score
Access
Action
Yes/No
Description
ID
ID
(m/m2/m3)
Type
(0,1,2,3)
Treatment
Type
(IA,OA,EA)
(A1,A2,A3)
of suspect material
(P/SP/ID)
(1,2,3)
(0,1,2,3)
(1,2,3)
GROUND
FLOOR (cont)
Tank Room 3
Yes
Ceiling – plasterboard
SP
-
-
-
-
-
NA
-
-
-
Walls – plaster over brick
SP
-
-
-
-
-
NA
-
-
-
Pipe insulation – MMMF
SP
-
-
-
-
-
NA
-
-
-
Hot water tank insulation –
SP
-
-
-
-
-
NA
-
-
-
MMMF
Floor – vinyl over concrete
SP
As
-
-
-
-
NA
-
-
-
BS/03
Sluice Room 2
Yes
Ceiling – plasterboard
SP
-
-
-
-
-
NA
-
-
-
Walls – plaster over brick
SP
-
-
-
-
-
NA
-
-
-
Toilet cisterns
SP
-
-
-
-
-
NA
-
-
-
Floor – vinyl over concrete
SP
-
-
-
-
-
NA
-
-
-
Level of ID: P – Presumed, SP – Strongly Presumed, ID – Identified.
Access: IA – Inaccessible, OA – Occasionally Accessed, EA – Easily/Regularly Accessed
Asbestos Type: NA – Non-Asbestos
Action: A1 – Remove ASAP, A2 – Repair/Encapsulate ASAP, A3 – Leave Undisturbed and Monitor Situation
Analyst – P Dean
Procedure ASB/6 APPENDIX B, Page 2 of 2, Issue No.5, Issue Date 23/01/03, Issued by VEGA
VEGA ENVIRONMENTAL CONSULTANTS LTD
APPENDIX A
ASBESTOS SURVEY - DATA RECORD SHEET - continued
Page 27
of 71
Opinions and interpretations expressed herein are outside the scope of UKAS accreditation held by VEGA
Report No: AR/04/1662
Date of survey: 13/10/04
Area ID
Surveyed
Location of sample point /
Level of
Sample
Extent
Product Condition
Surface
Asbestos
Score
Access
Action
Yes/No
Description
ID
ID
(m/m2/m3)
Type
(0,1,2,3)
Treatment
Type
(IA,OA,EA)
(A1,A2,A3)
of suspect material
(P/SP/ID)
(1,2,3)
(0,1,2,3)
(1,2,3)
GROUND
FLOOR (cont)
Store 2
Yes
Ceiling – plasterboard
SP
-
-
-
-
-
NA
-
-
-
Walls – plaster over brick
SP
-
-
-
-
-
NA
-
-
-
Electrical equipment
SP
-
-
-
-
-
NA
-
-
-
Floor – vinyl over concrete
SP
As
-
-
-
-
NA
-
-
-
BS/03
Store 3
Yes
Ceiling – plasterboard
SP
-
-
-
-
-
NA
-
-
-
Walls – plaster over brick
SP
-
-
-
-
-
NA
-
-
-
Electrical equipment
SP
-
-
-
-
-
NA
-
-
-
Floor – vinyl over concrete
SP
As
-
-
-
-
NA
-
-
-
BS/03
Level of ID: P – Presumed, SP – Strongly Presumed, ID – Identified.
Access: IA – Inaccessible, OA – Occasionally Accessed, EA – Easily/Regularly Accessed
Asbestos Type: NA – Non-Asbestos
Action: A1 – Remove ASAP, A2 – Repair/Encapsulate ASAP, A3 – Leave Undisturbed and Monitor Situation
Analyst – P Dean
Procedure ASB/6 APPENDIX B, Page 2 of 2, Issue No.5, Issue Date 23/01/03, Issued by VEGA
VEGA ENVIRONMENTAL CONSULTANTS LTD
APPENDIX A
ASBESTOS SURVEY - DATA RECORD SHEET - continued
Page 28
of 71
Opinions and interpretations expressed herein are outside the scope of UKAS accreditation held by VEGA
Report No: AR/04/1662
Date of survey: 13/10/04
Area ID
Surveyed
Location of sample point /
Level of
Sample
Extent
Product Condition
Surface
Asbestos
Score
Access
Action
Yes/No
Description
ID
ID
(m/m2/m3)
Type
(0,1,2,3)
Treatment
Type
(IA,OA,EA)
(A1,A2,A3)
of suspect material
(P/SP/ID)
(1,2,3)
(0,1,2,3)
(1,2,3)
GROUND
FLOOR (cont)
Kitchen 2
Yes
Ceiling – plasterboard
SP
-
-
-
-
-
NA
-
-
-
High level ceiling heater
SP
-
-
-
-
-
NA
-
-
-
Walls – ceramic tiles over brick
SP
-
-
-
-
-
NA
-
-
-
Door – window strip
SP
As
-
-
-
-
NA
-
-
-
BS/06
Hand basin – wood panel below
SP
-
-
-
-
-
NA
-
-
-
Floor – vinyl over concrete
SP
-
-
-
-
-
NA
-
-
-
Level of ID: P – Presumed, SP – Strongly Presumed, ID – Identified.
Access: IA – Inaccessible, OA – Occasionally Accessed, EA – Easily/Regularly Accessed
Asbestos Type: NA – Non-Asbestos
Action: A1 – Remove ASAP, A2 – Repair/Encapsulate ASAP, A3 – Leave Undisturbed and Monitor Situation
Analyst – P Dean
Procedure ASB/6 APPENDIX B, Page 2 of 2, Issue No.5, Issue Date 23/01/03, Issued by VEGA
VEGA ENVIRONMENTAL CONSULTANTS LTD
APPENDIX A
ASBESTOS SURVEY - DATA RECORD SHEET - continued
Page 29
of 71
Opinions and interpretations expressed herein are outside the scope of UKAS accreditation held by VEGA
Report No: AR/04/1662
Date of survey: 13/10/04
Area ID
Surveyed
Location of sample point /
Level of
Sample
Extent
Product Condition
Surface
Asbestos
Score
Access
Action
Yes/No
Description
ID
ID
(m/m2/m3)
Type
(0,1,2,3)
Treatment
Type
(IA,OA,EA)
(A1,A2,A3)
of suspect material
(P/SP/ID)
(1,2,3)
(0,1,2,3)
(1,2,3)
GROUND
FLOOR (cont)
Bedroom 9
Yes
Ceiling – plasterboard
SP
-
-
-
-
-
NA
-
-
-
Walls – plaster over brick
SP
-
-
-
-
-
NA
-
-
-
Floor – carpet over concrete
SP
-
-
-
-
-
NA
-
-
-
Bedroom 10
Yes
Ceiling – plasterboard
SP
-
-
-
-
-
NA
-
-
-
Walls – plaster over brick
SP
-
-
-
-
-
NA
-
-
-
Floor – carpet over concrete
SP
-
-
-
-
-
NA
-
-
-
Level of ID: P – Presumed, SP – Strongly Presumed, ID – Identified.
Access: IA – Inaccessible, OA – Occasionally Accessed, EA – Easily/Regularly Accessed
Asbestos Type: NA – Non-Asbestos
Action: A1 – Remove ASAP, A2 – Repair/Encapsulate ASAP, A3 – Leave Undisturbed and Monitor Situation
Analyst – P Dean
Procedure ASB/6 APPENDIX B, Page 2 of 2, Issue No.5, Issue Date 23/01/03, Issued by VEGA
VEGA ENVIRONMENTAL CONSULTANTS LTD
APPENDIX A
ASBESTOS SURVEY - DATA RECORD SHEET - continued
Page 30
of 71
Opinions and interpretations expressed herein are outside the scope of UKAS accreditation held by VEGA
Report No: AR/04/1662
Date of survey: 13/10/04
Area ID
Surveyed
Location of sample point /
Level of
Sample
Extent
Product Condition
Surface
Asbestos
Score
Access
Action
Yes/No
Description
ID
ID
(m/m2/m3)
Type
(0,1,2,3)
Treatment
Type
(IA,OA,EA)
(A1,A2,A3)
of suspect material
(P/SP/ID)
(1,2,3)
(0,1,2,3)
(1,2,3)
GROUND
FLOOR (cont)
Bedroom 11
Yes
Ceiling – plasterboard
SP
-
-
-
-
-
NA
-
-
-
Walls – plaster over brick
SP
-
-
-
-
-
NA
-
-
-
Floor – carpet over concrete
SP
-
-
-
-
-
NA
-
-
-
Bedroom 12
Yes
Ceiling – plasterboard
SP
-
-
-
-
-
NA
-
-
-
Walls – plaster over brick
SP
-
-
-
-
-
NA
-
-
-
Floor – carpet over concrete
SP
-
-
-
-
-
NA
-
-
-
Level of ID: P – Presumed, SP – Strongly Presumed, ID – Identified.
Access: IA – Inaccessible, OA – Occasionally Accessed, EA – Easily/Regularly Accessed
Asbestos Type: NA – Non-Asbestos
Action: A1 – Remove ASAP, A2 – Repair/Encapsulate ASAP, A3 – Leave Undisturbed and Monitor Situation
Analyst – P Dean
Procedure ASB/6 APPENDIX B, Page 2 of 2, Issue No.5, Issue Date 23/01/03, Issued by VEGA
VEGA ENVIRONMENTAL CONSULTANTS LTD
APPENDIX A
ASBESTOS SURVEY - DATA RECORD SHEET - continued
Page 31
of 71
Opinions and interpretations expressed herein are outside the scope of UKAS accreditation held by VEGA
Report No: AR/04/1662
Date of survey: 13/10/04
Area ID
Surveyed
Location of sample point /
Level of
Sample
Extent
Product Condition
Surface
Asbestos
Score
Access
Action
Yes/No
Description
ID
ID
(m/m2/m3)
Type
(0,1,2,3)
Treatment
Type
(IA,OA,EA)
(A1,A2,A3)
of suspect material
(P/SP/ID)
(1,2,3)
(0,1,2,3)
(1,2,3)
GROUND
FLOOR (cont)
Bedroom 13
Yes
Ceiling – plasterboard
SP
-
-
-
-
-
NA
-
-
-
Walls – plaster over brick
SP
-
-
-
-
-
NA
-
-
-
Floor – carpet over concrete
SP
-
-
-
-
-
NA
-
-
-
Bedroom 14
Yes
Ceiling – plasterboard
SP
-
-
-
-
-
NA
-
-
-
Walls – plaster over brick
SP
-
-
-
-
-
NA
-
-
-
Floor – carpet over concrete
SP
-
-
-
-
-
NA
-
-
-
Level of ID: P – Presumed, SP – Strongly Presumed, ID – Identified.
Access: IA – Inaccessible, OA – Occasionally Accessed, EA – Easily/Regularly Accessed
Asbestos Type: NA – Non-Asbestos
Action: A1 – Remove ASAP, A2 – Repair/Encapsulate ASAP, A3 – Leave Undisturbed and Monitor Situation
Analyst – P Dean
Procedure ASB/6 APPENDIX B, Page 2 of 2, Issue No.5, Issue Date 23/01/03, Issued by VEGA
VEGA ENVIRONMENTAL CONSULTANTS LTD
APPENDIX A
ASBESTOS SURVEY - DATA RECORD SHEET - continued
Page 32
of 71
Opinions and interpretations expressed herein are outside the scope of UKAS accreditation held by VEGA
Report No: AR/04/1662
Date of survey: 13/10/04
Area ID
Surveyed
Location of sample point /
Level of
Sample
Extent
Product Condition
Surface
Asbestos
Score
Access
Action
Yes/No
Description
ID
ID
(m/m2/m3)
Type
(0,1,2,3)
Treatment
Type
(IA,OA,EA)
(A1,A2,A3)
of suspect material
(P/SP/ID)
(1,2,3)
(0,1,2,3)
(1,2,3)
GROUND
FLOOR (cont)
Bedroom 15
Yes
Ceiling – plasterboard
SP
-
-
-
-
-
NA
-
-
-
Walls – plaster over brick
SP
-
-
-
-
-
NA
-
-
-
Floor – carpet over concrete
SP
-
-
-
-
-
NA
-
-
-
Bedroom 16
Yes
Ceiling – plasterboard
SP
-
-
-
-
-
NA
-
-
-
Walls – plaster over brick
SP
-
-
-
-
-
NA
-
-
-
Floor – carpet over concrete
SP
-
-
-
-
-
NA
-
-
-
Level of ID: P – Presumed, SP – Strongly Presumed, ID – Identified.
Access: IA – Inaccessible, OA – Occasionally Accessed, EA – Easily/Regularly Accessed
Asbestos Type: NA – Non-Asbestos
Action: A1 – Remove ASAP, A2 – Repair/Encapsulate ASAP, A3 – Leave Undisturbed and Monitor Situation
Analyst – P Dean
Procedure ASB/6 APPENDIX B, Page 2 of 2, Issue No.5, Issue Date 23/01/03, Issued by VEGA
VEGA ENVIRONMENTAL CONSULTANTS LTD
APPENDIX A
ASBESTOS SURVEY - DATA RECORD SHEET - continued
Page 33
of 71
Opinions and interpretations expressed herein are outside the scope of UKAS accreditation held by VEGA
Report No: AR/04/1662
Date of survey: 13/10/04
Area ID
Surveyed
Location of sample point /
Level of
Sample
Extent
Product Condition
Surface
Asbestos
Score
Access
Action
Yes/No
Description
ID
ID
(m/m2/m3)
Type
(0,1,2,3)
Treatment
Type
(IA,OA,EA)
(A1,A2,A3)
of suspect material
(P/SP/ID)
(1,2,3)
(0,1,2,3)
(1,2,3)
GROUND
FLOOR (cont)
Bathroom 2
Yes
Ceiling – plasterboard
SP
-
-
-
-
-
NA
-
-
-
Walls – ceramic tiles over brick
SP
-
-
-
-
-
NA
-
-
-
Corner and low level boxing
SP
-
-
-
-
-
NA
-
-
-
Floor – vinyl over concrete
SP
-
-
-
-
-
NA
-
-
-
Toilet 5
Yes
Ceiling – plasterboard
SP
-
-
-
-
-
NA
-
-
-
Walls – ceramic tiles over brick
SP
-
-
-
-
-
NA
-
-
-
Toilet cistern
SP
-
-
-
-
-
NA
-
-
-
Corner boxing
SP
-
-
-
-
-
NA
-
-
-
Floor – vinyl over concrete
SP
-
-
-
-
-
NA
-
-
-
Level of ID: P – Presumed, SP – Strongly Presumed, ID – Identified.
Access: IA – Inaccessible, OA – Occasionally Accessed, EA – Easily/Regularly Accessed
Asbestos Type: NA – Non-Asbestos
Action: A1 – Remove ASAP, A2 – Repair/Encapsulate ASAP, A3 – Leave Undisturbed and Monitor Situation
Analyst – P Dean
Procedure ASB/6 APPENDIX B, Page 2 of 2, Issue No.5, Issue Date 23/01/03, Issued by VEGA
VEGA ENVIRONMENTAL CONSULTANTS LTD
APPENDIX A
ASBESTOS SURVEY - DATA RECORD SHEET - continued
Page 34
of 71
Opinions and interpretations expressed herein are outside the scope of UKAS accreditation held by VEGA
Report No: AR/04/1662
Date of survey: 13/10/04
Area ID
Surveyed
Location of sample point /
Level of
Sample
Extent
Product Condition
Surface
Asbestos
Score
Access
Action
Yes/No
Description
ID
ID
(m/m2/m3)
Type
(0,1,2,3)
Treatment
Type
(IA,OA,EA)
(A1,A2,A3)
of suspect material
(P/SP/ID)
(1,2,3)
(0,1,2,3)
(1,2,3)
GROUND
FLOOR (cont)
Toilet 6
Yes
Ceiling – plasterboard
SP
-
-
-
-
-
NA
-
-
-
Walls – ceramic tiles over brick
SP
-
-
-
-
-
NA
-
-
-
Toilet cistern
SP
-
-
-
-
-
NA
-
-
-
Corner boxing
SP
-
-
-
-
-
NA
-
-
-
Floor – vinyl over concrete
SP
-
-
-
-
-
NA
-
-
-
Lounge 2
Yes
Ceiling – plasterboard
SP
-
-
-
-
-
NA
-
-
-
Walls – plaster over brick
SP
-
-
-
-
-
NA
-
-
-
Floor – carpet over concrete
SP
-
-
-
-
-
NA
-
-
-
Level of ID: P – Presumed, SP – Strongly Presumed, ID – Identified.
Access: IA – Inaccessible, OA – Occasionally Accessed, EA – Easily/Regularly Accessed
Asbestos Type: NA – Non-Asbestos
Action: A1 – Remove ASAP, A2 – Repair/Encapsulate ASAP, A3 – Leave Undisturbed and Monitor Situation
Analyst – P Dean
Procedure ASB/6 APPENDIX B, Page 2 of 2, Issue No.5, Issue Date 23/01/03, Issued by VEGA
VEGA ENVIRONMENTAL CONSULTANTS LTD
APPENDIX A
ASBESTOS SURVEY - DATA RECORD SHEET - continued
Page 35
of 71
Opinions and interpretations expressed herein are outside the scope of UKAS accreditation held by VEGA
Report No: AR/04/1662
Date of survey: 13/10/04
Area ID
Surveyed
Location of sample point /
Level of
Sample
Extent
Product Condition
Surface
Asbestos
Score
Access
Action
Yes/No
Description
ID
ID
(m/m2/m3)
Type
(0,1,2,3)
Treatment
Type
(IA,OA,EA)
(A1,A2,A3)
of suspect material
(P/SP/ID)
(1,2,3)
(0,1,2,3)
(1,2,3)
GROUND
FLOOR (cont)
Void above
Yes
Roof – internal loft insulation
SP
As
-
-
-
-
NA
-
-
-
Rooms adjacent
BS/02
Corridor 3
Walls – brick
SP
-
-
-
-
-
NA
-
-
-
Pipe insulation – MMMF
SP
-
-
-
-
-
NA
-
-
-
Loft insulation – MMMF
SP
-
-
-
-
-
NA
-
-
-
Water tank insulation –
SP
-
-
-
-
-
NA
-
-
-
polystyrene
Corridor 4
Yes
Ceiling – plasterboard
SP
-
-
-
-
-
NA
-
-
-
Walls – plaster over brick
SP
-
-
-
-
-
NA
-
-
-
Floor – carpet over concrete
SP
-
-
-
-
-
NA
-
-
-
Level of ID: P – Presumed, SP – Strongly Presumed, ID – Identified.
Access: IA – Inaccessible, OA – Occasionally Accessed, EA – Easily/Regularly Accessed
Asbestos Type: NA – Non-Asbestos
Action: A1 – Remove ASAP, A2 – Repair/Encapsulate ASAP, A3 – Leave Undisturbed and Monitor Situation
Analyst – P Dean
Procedure ASB/6 APPENDIX B, Page 2 of 2, Issue No.5, Issue Date 23/01/03, Issued by VEGA
VEGA ENVIRONMENTAL CONSULTANTS LTD
APPENDIX A
ASBESTOS SURVEY - DATA RECORD SHEET - continued
Page 36
of 71
Opinions and interpretations expressed herein are outside the scope of UKAS accreditation held by VEGA
Report No: AR/04/1662
Date of survey: 13/10/04
Area ID
Surveyed
Location of sample point /
Level of
Sample
Extent
Product Condition
Surface
Asbestos
Score
Access
Action
Yes/No
Description
ID
ID
(m/m2/m3)
Type
(0,1,2,3)
Treatment
Type
(IA,OA,EA)
(A1,A2,A3)
of suspect material
(P/SP/ID)
(1,2,3)
(0,1,2,3)
(1,2,3)
GROUND
FLOOR (cont)
Void above
Yes
Roof – internal loft insulation
SP
As
-
-
-
-
NA
-
-
-
BS/02
Walls – brick
SP
-
-
-
-
-
NA
-
-
-
Pipe insulation – MMMF
SP
-
-
-
-
-
NA
-
-
-
Loft insulation – MMMF
SP
-
-
-
-
-
NA
-
-
-
Water tank insulation –
SP
-
-
-
-
-
NA
-
-
-
polystyrene
Level of ID: P – Presumed, SP – Strongly Presumed, ID – Identified.
Access: IA – Inaccessible, OA – Occasionally Accessed, EA – Easily/Regularly Accessed
Asbestos Type: NA – Non-Asbestos
Action: A1 – Remove ASAP, A2 – Repair/Encapsulate ASAP, A3 – Leave Undisturbed and Monitor Situation
Analyst – P Dean
Procedure ASB/6 APPENDIX B, Page 2 of 2, Issue No.5, Issue Date 23/01/03, Issued by VEGA
VEGA ENVIRONMENTAL CONSULTANTS LTD
APPENDIX A
ASBESTOS SURVEY - DATA RECORD SHEET - continued
Page 37
of 71
Opinions and interpretations expressed herein are outside the scope of UKAS accreditation held by VEGA
Report No: AR/04/1662
Date of survey: 13/10/04
Area ID
Surveyed
Location of sample point /
Level of
Sample
Extent
Product Condition
Surface
Asbestos
Score
Access
Action
Yes/No
Description
ID
ID
(m/m2/m3)
Type
(0,1,2,3)
Treatment
Type
(IA,OA,EA)
(A1,A2,A3)
of suspect material
(P/SP/ID)
(1,2,3)
(0,1,2,3)
(1,2,3)
GROUND
FLOOR (cont)
Tank Room 4
Yes
Ceiling – plasterboard
SP
-
-
-
-
-
NA
-
-
-
Walls – plaster over brick
SP
-
-
-
-
-
NA
-
-
-
Pipe insulation – MMMF
SP
-
-
-
-
-
NA
-
-
-
Hot water tank insulation –
SP
-
-
-
-
-
NA
-
-
-
MMMF
Floor – vinyl over concrete
SP
As
-
-
-
-
NA
-
-
-
BS/03
Store 4
Yes
Ceiling – plasterboard
SP
-
-
-
-
-
NA
-
-
-
Walls – plaster over brick
SP
-
-
-
-
-
NA
-
-
-
Electrical equipment
SP
-
-
-
-
-
NA
-
-
-
Floor – vinyl over concrete
SP
As
-
-
-
-
NA
-
-
-
BS/03
Level of ID: P – Presumed, SP – Strongly Presumed, ID – Identified.
Access: IA – Inaccessible, OA – Occasionally Accessed, EA – Easily/Regularly Accessed
Asbestos Type: NA – Non-Asbestos
Action: A1 – Remove ASAP, A2 – Repair/Encapsulate ASAP, A3 – Leave Undisturbed and Monitor Situation
Analyst – P Dean
Procedure ASB/6 APPENDIX B, Page 2 of 2, Issue No.5, Issue Date 23/01/03, Issued by VEGA
VEGA ENVIRONMENTAL CONSULTANTS LTD
APPENDIX A
ASBESTOS SURVEY - DATA RECORD SHEET - continued
Page 38
of 71
Opinions and interpretations expressed herein are outside the scope of UKAS accreditation held by VEGA
Report No: AR/04/1662
Date of survey: 13/10/04
Area ID
Surveyed
Location of sample point /
Level of
Sample
Extent
Product Condition
Surface
Asbestos
Score
Access
Action
Yes/No
Description
ID
ID
(m/m2/m3)
Type
(0,1,2,3)
Treatment
Type
(IA,OA,EA)
(A1,A2,A3)
of suspect material
(P/SP/ID)
(1,2,3)
(0,1,2,3)
(1,2,3)
GROUND
FLOOR (cont)
Store 5
Yes
Ceiling – plasterboard
SP
-
-
-
-
-
NA
-
-
-
Walls – plaster over brick
SP
-
-
-
-
-
NA
-
-
-
Electrical equipment
SP
-
-
-
-
-
NA
-
-
-
Floor – vinyl over concrete
SP
As
-
-
-
-
NA
-
-
-
BS/03
Toilet 7
Yes
Ceiling – plasterboard
SP
-
-
-
-
-
NA
-
-
-
Walls – ceramic tiles over brick
SP
-
-
-
-
-
NA
-
-
-
Toilet cistern
SP
-
-
-
-
-
NA
-
-
-
Corner boxing
SP
-
-
-
-
-
NA
-
-
-
Floor – vinyl over concrete
SP
-
-
-
-
-
NA
-
-
-
Level of ID: P – Presumed, SP – Strongly Presumed, ID – Identified.
Access: IA – Inaccessible, OA – Occasionally Accessed, EA – Easily/Regularly Accessed
Asbestos Type: NA – Non-Asbestos
Action: A1 – Remove ASAP, A2 – Repair/Encapsulate ASAP, A3 – Leave Undisturbed and Monitor Situation
Analyst – P Dean
Procedure ASB/6 APPENDIX B, Page 2 of 2, Issue No.5, Issue Date 23/01/03, Issued by VEGA
VEGA ENVIRONMENTAL CONSULTANTS LTD
APPENDIX A
ASBESTOS SURVEY - DATA RECORD SHEET - continued
Page 39
of 71
Opinions and interpretations expressed herein are outside the scope of UKAS accreditation held by VEGA
Report No: AR/04/1662
Date of survey: 13/10/04
Area ID
Surveyed
Location of sample point /
Level of
Sample
Extent
Product Condition
Surface
Asbestos
Score
Access
Action
Yes/No
Description
ID
ID
(m/m2/m3)
Type
(0,1,2,3)
Treatment
Type
(IA,OA,EA)
(A1,A2,A3)
of suspect material
(P/SP/ID)
(1,2,3)
(0,1,2,3)
(1,2,3)
GROUND
FLOOR (cont)
Sluice Room 3
Yes
Ceiling – plasterboard
SP
-
-
-
-
-
NA
-
-
-
Walls – plaster over brick
SP
-
-
-
-
-
NA
-
-
-
Toilet cisterns
SP
-
-
-
-
-
NA
-
-
-
Floor – vinyl over concrete
SP
-
-
-
-
-
NA
-
-
-
Dining Room 3
Yes
Ceiling – textured coating
ID
BS/07
-
-
-
-
NA
-
-
-
Walls – plaster over brick
SP
-
-
-
-
-
NA
-
-
-
Floor – carpet over concrete
SP
-
-
-
-
-
NA
-
-
-
Level of ID: P – Presumed, SP – Strongly Presumed, ID – Identified.
Access: IA – Inaccessible, OA – Occasionally Accessed, EA – Easily/Regularly Accessed
Asbestos Type: NA – Non-Asbestos
Action: A1 – Remove ASAP, A2 – Repair/Encapsulate ASAP, A3 – Leave Undisturbed and Monitor Situation
Analyst – P Dean
Procedure ASB/6 APPENDIX B, Page 2 of 2, Issue No.5, Issue Date 23/01/03, Issued by VEGA
VEGA ENVIRONMENTAL CONSULTANTS LTD
APPENDIX A
ASBESTOS SURVEY - DATA RECORD SHEET - continued
Page 40
of 71
Opinions and interpretations expressed herein are outside the scope of UKAS accreditation held by VEGA
Report No: AR/04/1662
Date of survey: 13/10/04
Area ID
Surveyed
Location of sample point /
Level of
Sample
Extent
Product Condition
Surface
Asbestos
Score
Access
Action
Yes/No
Description
ID
ID
(m/m2/m3)
Type
(0,1,2,3)
Treatment
Type
(IA,OA,EA)
(A1,A2,A3)
of suspect material
(P/SP/ID)
(1,2,3)
(0,1,2,3)
(1,2,3)
GROUND
FLOOR (cont)
Kitchen 3
Yes
Ceiling – plasterboard
SP
-
-
-
-
-
NA
-
-
-
High level ceiling heater
SP
-
-
-
-
-
NA
-
-
-
Walls – ceramic tiles over brick
SP
-
-
-
-
-
NA
-
-
-
Door – window strip
SP
As
-
-
-
-
NA
-
-
-
BS/06
Hand basin – wood panel below
SP
-
-
-
-
-
NA
-
-
-
Floor – vinyl over concrete
SP
-
-
-
-
-
NA
-
-
-
Bedroom 17
Yes
Ceiling – plasterboard
SP
-
-
-
-
-
NA
-
-
-
Walls – plaster over brick
SP
-
-
-
-
-
NA
-
-
-
Floor – carpet over concrete
SP
-
-
-
-
-
NA
-
-
-
Level of ID: P – Presumed, SP – Strongly Presumed, ID – Identified.
Access: IA – Inaccessible, OA – Occasionally Accessed, EA – Easily/Regularly Accessed
Asbestos Type: NA – Non-Asbestos
Action: A1 – Remove ASAP, A2 – Repair/Encapsulate ASAP, A3 – Leave Undisturbed and Monitor Situation
Analyst – P Dean
Procedure ASB/6 APPENDIX B, Page 2 of 2, Issue No.5, Issue Date 23/01/03, Issued by VEGA
VEGA ENVIRONMENTAL CONSULTANTS LTD
APPENDIX A
ASBESTOS SURVEY - DATA RECORD SHEET - continued
Page 41
of 71
Opinions and interpretations expressed herein are outside the scope of UKAS accreditation held by VEGA
Report No: AR/04/1662
Date of survey: 13/10/04
Area ID
Surveyed
Location of sample point /
Level of
Sample
Extent
Product Condition
Surface
Asbestos
Score
Access
Action
Yes/No
Description
ID
ID
(m/m2/m3)
Type
(0,1,2,3)
Treatment
Type
(IA,OA,EA)
(A1,A2,A3)
of suspect material
(P/SP/ID)
(1,2,3)
(0,1,2,3)
(1,2,3)
GROUND
FLOOR (cont)
Bedroom 18
Yes
Ceiling – plasterboard
SP
-
-
-
-
-
NA
-
-
-
Walls – plaster over brick
SP
-
-
-
-
-
NA
-
-
-
Floor – carpet over concrete
SP
-
-
-
-
-
NA
-
-
-
Bedroom 19
Yes
Ceiling – plasterboard
SP
-
-
-
-
-
NA
-
-
-
Walls – plaster over brick
SP
-
-
-
-
-
NA
-
-
-
Floor – carpet over concrete
SP
-
-
-
-
-
NA
-
-
-
Bedroom 20
Yes
Ceiling – plasterboard
SP
-
-
-
-
-
NA
-
-
-
Walls – plaster over brick
SP
-
-
-
-
-
NA
-
-
-
Floor – carpet over concrete
SP
-
-
-
-
-
NA
-
-
-
Level of ID: P – Presumed, SP – Strongly Presumed, ID – Identified.
Access: IA – Inaccessible, OA – Occasionally Accessed, EA – Easily/Regularly Accessed
Asbestos Type: NA – Non-Asbestos
Action: A1 – Remove ASAP, A2 – Repair/Encapsulate ASAP, A3 – Leave Undisturbed and Monitor Situation
Analyst – P Dean
Procedure ASB/6 APPENDIX B, Page 2 of 2, Issue No.5, Issue Date 23/01/03, Issued by VEGA
VEGA ENVIRONMENTAL CONSULTANTS LTD
APPENDIX A
ASBESTOS SURVEY - DATA RECORD SHEET - continued
Page 42
of 71
Opinions and interpretations expressed herein are outside the scope of UKAS accreditation held by VEGA
Report No: AR/04/1662
Date of survey: 13/10/04
Area ID
Surveyed
Location of sample point /
Level of
Sample
Extent
Product Condition
Surface
Asbestos
Score
Access
Action
Yes/No
Description
ID
ID
(m/m2/m3)
Type
(0,1,2,3)
Treatment
Type
(IA,OA,EA)
(A1,A2,A3)
of suspect material
(P/SP/ID)
(1,2,3)
(0,1,2,3)
(1,2,3)
GROUND
FLOOR (cont)
Bedroom 21
Yes
Ceiling – plasterboard
SP
-
-
-
-
-
NA
-
-
-
Walls – plaster over brick
SP
-
-
-
-
-
NA
-
-
-
Floor – carpet over concrete
SP
-
-
-
-
-
NA
-
-
-
Bedroom 22
Yes
Ceiling – plasterboard
SP
-
-
-
-
-
NA
-
-
-
Walls – plaster over brick
SP
-
-
-
-
-
NA
-
-
-
Floor – carpet over concrete
SP
-
-
-
-
-
NA
-
-
-
Bedroom 23
Yes
Ceiling – plasterboard
SP
-
-
-
-
-
NA
-
-
-
Walls – plaster over brick
SP
-
-
-
-
-
NA
-
-
-
Floor – carpet over concrete
SP
-
-
-
-
-
NA
-
-
-
Level of ID: P – Presumed, SP – Strongly Presumed, ID – Identified.
Access: IA – Inaccessible, OA – Occasionally Accessed, EA – Easily/Regularly Accessed
Asbestos Type: NA – Non-Asbestos
Action: A1 – Remove ASAP, A2 – Repair/Encapsulate ASAP, A3 – Leave Undisturbed and Monitor Situation
Analyst – P Dean
Procedure ASB/6 APPENDIX B, Page 2 of 2, Issue No.5, Issue Date 23/01/03, Issued by VEGA
VEGA ENVIRONMENTAL CONSULTANTS LTD
APPENDIX A
ASBESTOS SURVEY - DATA RECORD SHEET - continued
Page 43
of 71
Opinions and interpretations expressed herein are outside the scope of UKAS accreditation held by VEGA
Report No: AR/04/1662
Date of survey: 13/10/04
Area ID
Surveyed
Location of sample point /
Level of
Sample
Extent
Product Condition
Surface
Asbestos
Score
Access
Action
Yes/No
Description
ID
ID
(m/m2/m3)
Type
(0,1,2,3)
Treatment
Type
(IA,OA,EA)
(A1,A2,A3)
of suspect material
(P/SP/ID)
(1,2,3)
(0,1,2,3)
(1,2,3)
GROUND
FLOOR (cont)
Bedroom 24
Yes
Ceiling – plasterboard
SP
-
-
-
-
-
NA
-
-
-
Walls – plaster over brick
SP
-
-
-
-
-
NA
-
-
-
Floor – carpet over concrete
SP
-
-
-
-
-
NA
-
-
-
Bathroom 3
Yes
Ceiling – plasterboard
SP
-
-
-
-
-
NA
-
-
-
Walls – ceramic tiles over brick
SP
-
-
-
-
-
NA
-
-
-
Corner and low level boxing
SP
-
-
-
-
-
NA
-
-
-
Floor – vinyl over concrete
SP
-
-
-
-
-
NA
-
-
-
Level of ID: P – Presumed, SP – Strongly Presumed, ID – Identified.
Access: IA – Inaccessible, OA – Occasionally Accessed, EA – Easily/Regularly Accessed
Asbestos Type: NA – Non-Asbestos
Action: A1 – Remove ASAP, A2 – Repair/Encapsulate ASAP, A3 – Leave Undisturbed and Monitor Situation
Analyst – P Dean
Procedure ASB/6 APPENDIX B, Page 2 of 2, Issue No.5, Issue Date 23/01/03, Issued by VEGA
VEGA ENVIRONMENTAL CONSULTANTS LTD
APPENDIX A
ASBESTOS SURVEY - DATA RECORD SHEET - continued
Page 44
of 71
Opinions and interpretations expressed herein are outside the scope of UKAS accreditation held by VEGA
Report No: AR/04/1662
Date of survey: 13/10/04
Area ID
Surveyed
Location of sample point /
Level of
Sample
Extent
Product Condition
Surface
Asbestos
Score
Access
Action
Yes/No
Description
ID
ID
(m/m2/m3)
Type
(0,1,2,3)
Treatment
Type
(IA,OA,EA)
(A1,A2,A3)
of suspect material
(P/SP/ID)
(1,2,3)
(0,1,2,3)
(1,2,3)
GROUND
FLOOR (cont)
Lounge 3
Yes
Ceiling – plasterboard
SP
-
-
-
-
-
NA
-
-
-
Walls – plaster over brick
SP
-
-
-
-
-
NA
-
-
-
Floor – carpet over concrete
SP
-
-
-
-
-
NA
-
-
-
Toilet 8
Yes
Ceiling – plasterboard
SP
-
-
-
-
-
NA
-
-
-
Walls – ceramic tiles over brick
SP
-
-
-
-
-
NA
-
-
-
Toilet cistern
SP
-
-
-
-
-
NA
-
-
-
Corner boxing
SP
-
-
-
-
-
NA
-
-
-
Floor – vinyl over concrete
SP
-
-
-
-
-
NA
-
-
-
Level of ID: P – Presumed, SP – Strongly Presumed, ID – Identified.
Access: IA – Inaccessible, OA – Occasionally Accessed, EA – Easily/Regularly Accessed
Asbestos Type: NA – Non-Asbestos
Action: A1 – Remove ASAP, A2 – Repair/Encapsulate ASAP, A3 – Leave Undisturbed and Monitor Situation
Analyst – P Dean
Procedure ASB/6 APPENDIX B, Page 2 of 2, Issue No.5, Issue Date 23/01/03, Issued by VEGA
VEGA ENVIRONMENTAL CONSULTANTS LTD
APPENDIX A
ASBESTOS SURVEY - DATA RECORD SHEET - continued
Page 45
of 71
Opinions and interpretations expressed herein are outside the scope of UKAS accreditation held by VEGA
Report No: AR/04/1662
Date of survey: 13/10/04
Area ID
Surveyed
Location of sample point /
Level of
Sample
Extent
Product Condition
Surface
Asbestos
Score
Access
Action
Yes/No
Description
ID
ID
(m/m2/m3)
Type
(0,1,2,3)
Treatment
Type
(IA,OA,EA)
(A1,A2,A3)
of suspect material
(P/SP/ID)
(1,2,3)
(0,1,2,3)
(1,2,3)
GROUND
FLOOR (cont)
Toilet 9
Yes
Ceiling – plasterboard
SP
-
-
-
-
-
NA
-
-
-
Walls – ceramic tiles over brick
SP
-
-
-
-
-
NA
-
-
-
Toilet cistern
SP
-
-
-
-
-
NA
-
-
-
Corner boxing
SP
-
-
-
-
-
NA
-
-
-
Floor – vinyl over concrete
SP
-
-
-
-
-
NA
-
-
-
Level of ID: P – Presumed, SP – Strongly Presumed, ID – Identified.
Access: IA – Inaccessible, OA – Occasionally Accessed, EA – Easily/Regularly Accessed
Asbestos Type: NA – Non-Asbestos
Action: A1 – Remove ASAP, A2 – Repair/Encapsulate ASAP, A3 – Leave Undisturbed and Monitor Situation
Analyst – P Dean
Procedure ASB/6 APPENDIX B, Page 2 of 2, Issue No.5, Issue Date 23/01/03, Issued by VEGA
VEGA ENVIRONMENTAL CONSULTANTS LTD
APPENDIX A
ASBESTOS SURVEY - DATA RECORD SHEET - continued
Page 46
of 71
Opinions and interpretations expressed herein are outside the scope of UKAS accreditation held by VEGA
Report No: AR/04/1662
Date of survey: 13/10/04
Area ID
Surveyed
Location of sample point /
Level of
Sample
Extent
Product Condition
Surface
Asbestos
Score
Access
Action
Yes/No
Description
ID
ID
(m/m2/m3)
Type
(0,1,2,3)
Treatment
Type
(IA,OA,EA)
(A1,A2,A3)
of suspect material
(P/SP/ID)
(1,2,3)
(0,1,2,3)
(1,2,3)
GROUND
FLOOR (cont)
Void above
Yes
Roof – internal loft insulation
SP
As
-
-
-
-
NA
-
-
-
Rooms adjacent
BS/02
Corridor 4
Walls – brick
SP
-
-
-
-
-
NA
-
-
-
Pipe insulation – MMMF
SP
-
-
-
-
-
NA
-
-
-
Loft insulation – MMMF
SP
-
-
-
-
-
NA
-
-
-
Water tank insulation –
SP
-
-
-
-
-
NA
-
-
-
polystyrene
Corridor 5
Yes
Ceiling – plasterboard
SP
-
-
-
-
-
NA
-
-
-
Walls – plaster over brick
SP
-
-
-
-
-
NA
-
-
-
Floor – carpet over concrete
SP
-
-
-
-
-
NA
-
-
-
Level of ID: P – Presumed, SP – Strongly Presumed, ID – Identified.
Access: IA – Inaccessible, OA – Occasionally Accessed, EA – Easily/Regularly Accessed
Asbestos Type: NA – Non-Asbestos
Action: A1 – Remove ASAP, A2 – Repair/Encapsulate ASAP, A3 – Leave Undisturbed and Monitor Situation
Analyst – P Dean
Procedure ASB/6 APPENDIX B, Page 2 of 2, Issue No.5, Issue Date 23/01/03, Issued by VEGA
VEGA ENVIRONMENTAL CONSULTANTS LTD
APPENDIX A
ASBESTOS SURVEY - DATA RECORD SHEET - continued
Page 47
of 71
Opinions and interpretations expressed herein are outside the scope of UKAS accreditation held by VEGA
Report No: AR/04/1662
Date of survey: 13/10/04
Area ID
Surveyed
Location of sample point /
Level of
Sample
Extent
Product Condition
Surface
Asbestos
Score
Access
Action
Yes/No
Description
ID
ID
(m/m2/m3)
Type
(0,1,2,3)
Treatment
Type
(IA,OA,EA)
(A1,A2,A3)
of suspect material
(P/SP/ID)
(1,2,3)
(0,1,2,3)
(1,2,3)
GROUND
FLOOR (cont)
Void above
Yes
Roof – internal loft insulation
SP
As
-
-
-
-
NA
-
-
-
BS/02
Walls – brick
SP
-
-
-
-
-
NA
-
-
-
Pipe insulation – MMMF
SP
-
-
-
-
-
NA
-
-
-
Loft insulation – MMMF
SP
-
-
-
-
-
NA
-
-
-
Water tank insulation –
SP
-
-
-
-
-
NA
-
-
-
polystyrene
Partition wall
SP
As
-
-
-
-
NA
-
-
-
BS/06
Level of ID: P – Presumed, SP – Strongly Presumed, ID – Identified.
Access: IA – Inaccessible, OA – Occasionally Accessed, EA – Easily/Regularly Accessed
Asbestos Type: NA – Non-Asbestos
Action: A1 – Remove ASAP, A2 – Repair/Encapsulate ASAP, A3 – Leave Undisturbed and Monitor Situation
Analyst – P Dean
Procedure ASB/6 APPENDIX B, Page 2 of 2, Issue No.5, Issue Date 23/01/03, Issued by VEGA
VEGA ENVIRONMENTAL CONSULTANTS LTD
APPENDIX A
ASBESTOS SURVEY - DATA RECORD SHEET - continued
Page 48
of 71
Opinions and interpretations expressed herein are outside the scope of UKAS accreditation held by VEGA
Report No: AR/04/1662
Date of survey: 13/10/04
Area ID
Surveyed
Location of sample point /
Level of
Sample
Extent
Product Condition
Surface
Asbestos
Score
Access
Action
Yes/No
Description
ID
ID
(m/m2/m3)
Type
(0,1,2,3)
Treatment
Type
(IA,OA,EA)
(A1,A2,A3)
of suspect material
(P/SP/ID)
(1,2,3)
(0,1,2,3)
(1,2,3)
GROUND
FLOOR (cont)
Hairdresser’s
Yes
Ceiling – plasterboard
SP
-
-
-
-
-
NA
-
-
-
Walls – plaster over brick and
SP
-
-
-
-
-
NA
-
-
-
ceramic tiles
Corner and low level boxing
SP
-
-
-
-
-
NA
-
-
-
Notice board
SP
-
-
-
-
-
NA
-
-
-
Floor – vinyl over concrete
SP
As
-
-
-
-
NA
-
-
-
BS/03
Toilet 10
Yes
Ceiling – plasterboard
SP
-
-
-
-
-
NA
-
-
-
Walls – ceramic tiles over brick
SP
-
-
-
-
-
NA
-
-
-
Toilet cistern
SP
-
-
-
-
-
NA
-
-
-
Corner boxing
SP
-
-
-
-
-
NA
-
-
-
Floor – vinyl over concrete
SP
-
-
-
-
-
NA
-
-
-
Level of ID: P – Presumed, SP – Strongly Presumed, ID – Identified.
Access: IA – Inaccessible, OA – Occasionally Accessed, EA – Easily/Regularly Accessed
Asbestos Type: NA – Non-Asbestos
Action: A1 – Remove ASAP, A2 – Repair/Encapsulate ASAP, A3 – Leave Undisturbed and Monitor Situation
Analyst – P Dean
Procedure ASB/6 APPENDIX B, Page 2 of 2, Issue No.5, Issue Date 23/01/03, Issued by VEGA
VEGA ENVIRONMENTAL CONSULTANTS LTD
APPENDIX A
ASBESTOS SURVEY - DATA RECORD SHEET - continued
Page 49
of 71
Opinions and interpretations expressed herein are outside the scope of UKAS accreditation held by VEGA
Report No: AR/04/1662
Date of survey: 13/10/04
Area ID
Surveyed
Location of sample point /
Level of
Sample
Extent
Product Condition
Surface
Asbestos
Score
Access
Action
Yes/No
Description
ID
ID
(m/m2/m3)
Type
(0,1,2,3)
Treatment
Type
(IA,OA,EA)
(A1,A2,A3)
of suspect material
(P/SP/ID)
(1,2,3)
(0,1,2,3)
(1,2,3)
GROUND
FLOOR (cont)
Smoking Room
Yes
Ceiling – plasterboard
SP
-
-
-
-
-
NA
-
-
-
Walls – plaster over brick
SP
-
-
-
-
-
NA
-
-
-
Floor – carpet over concrete
SP
-
-
-
-
-
NA
-
-
-
Day Centre
Yes
Ceiling – textured coating
SP
As
-
-
-
-
NA
-
-
-
BS/07
Walls – plaster over brick
SP
-
-
-
-
-
NA
-
-
-
Notice board
SP
-
-
-
-
-
NA
-
-
-
Floor – carpet over concrete
SP
-
-
-
-
-
NA
-
-
-
Level of ID: P – Presumed, SP – Strongly Presumed, ID – Identified.
Access: IA – Inaccessible, OA – Occasionally Accessed, EA – Easily/Regularly Accessed
Asbestos Type: NA – Non-Asbestos
Action: A1 – Remove ASAP, A2 – Repair/Encapsulate ASAP, A3 – Leave Undisturbed and Monitor Situation
Analyst – P Dean
Procedure ASB/6 APPENDIX B, Page 2 of 2, Issue No.5, Issue Date 23/01/03, Issued by VEGA
VEGA ENVIRONMENTAL CONSULTANTS LTD
APPENDIX A
ASBESTOS SURVEY - DATA RECORD SHEET - continued
Page 50
of 71
Opinions and interpretations expressed herein are outside the scope of UKAS accreditation held by VEGA
Report No: AR/04/1662
Date of survey: 13/10/04
Area ID
Surveyed
Location of sample point /
Level of
Sample
Extent
Product Condition
Surface
Asbestos
Score
Access
Action
Yes/No
Description
ID
ID
(m/m2/m3)
Type
(0,1,2,3)
Treatment
Type
(IA,OA,EA)
(A1,A2,A3)
of suspect material
(P/SP/ID)
(1,2,3)
(0,1,2,3)
(1,2,3)
GROUND
FLOOR (cont)
Tank Room 5
Yes
Ceiling – plasterboard
SP
-
-
-
-
-
NA
-
-
-
Walls – plaster over brick
SP
-
-
-
-
-
NA
-
-
-
Pipe insulation – MMMF
SP
-
-
-
-
-
NA
-
-
-
Hot water tank insulation –
SP
-
-
-
-
-
NA
-
-
-
MMMF
Floor – vinyl over concrete
SP
As
-
-
-
-
NA
-
-
-
BS/03
Store 6
Yes
Ceiling – plasterboard
SP
-
-
-
-
-
NA
-
-
-
Walls – plaster over brick
SP
-
-
-
-
-
NA
-
-
-
Electrical equipment
SP
-
-
-
-
-
NA
-
-
-
Floor – vinyl over concrete
SP
As
-
-
-
-
NA
-
-
-
BS/03
Level of ID: P – Presumed, SP – Strongly Presumed, ID – Identified.
Access: IA – Inaccessible, OA – Occasionally Accessed, EA – Easily/Regularly Accessed
Asbestos Type: NA – Non-Asbestos
Action: A1 – Remove ASAP, A2 – Repair/Encapsulate ASAP, A3 – Leave Undisturbed and Monitor Situation
Analyst – P Dean
Procedure ASB/6 APPENDIX B, Page 2 of 2, Issue No.5, Issue Date 23/01/03, Issued by VEGA
VEGA ENVIRONMENTAL CONSULTANTS LTD
APPENDIX A
ASBESTOS SURVEY - DATA RECORD SHEET - continued
Page 51
of 71
Opinions and interpretations expressed herein are outside the scope of UKAS accreditation held by VEGA
Report No: AR/04/1662
Date of survey: 13/10/04
Area ID
Surveyed
Location of sample point /
Level of
Sample
Extent
Product Condition
Surface
Asbestos
Score
Access
Action
Yes/No
Description
ID
ID
(m/m2/m3)
Type
(0,1,2,3)
Treatment
Type
(IA,OA,EA)
(A1,A2,A3)
of suspect material
(P/SP/ID)
(1,2,3)
(0,1,2,3)
(1,2,3)
GROUND
FLOOR (cont)
Toilet 11
Yes
Ceiling – plasterboard
SP
-
-
-
-
-
NA
-
-
-
Walls – ceramic tiles over brick
SP
-
-
-
-
-
NA
-
-
-
Toilet cistern
SP
-
-
-
-
-
NA
-
-
-
Corner boxing
SP
-
-
-
-
-
NA
-
-
-
Floor – vinyl over concrete
SP
-
-
-
-
-
NA
-
-
-
Toilet 12
Yes
Ceiling – plasterboard
SP
-
-
-
-
-
NA
-
-
-
Walls – ceramic tiles over brick
SP
-
-
-
-
-
NA
-
-
-
Toilet cistern
SP
-
-
-
-
-
NA
-
-
-
Corner boxing
SP
-
-
-
-
-
NA
-
-
-
Floor – vinyl over concrete
SP
-
-
-
-
-
NA
-
-
-
Level of ID: P – Presumed, SP – Strongly Presumed, ID – Identified.
Access: IA – Inaccessible, OA – Occasionally Accessed, EA – Easily/Regularly Accessed
Asbestos Type: NA – Non-Asbestos
Action: A1 – Remove ASAP, A2 – Repair/Encapsulate ASAP, A3 – Leave Undisturbed and Monitor Situation
Analyst – P Dean
Procedure ASB/6 APPENDIX B, Page 2 of 2, Issue No.5, Issue Date 23/01/03, Issued by VEGA
VEGA ENVIRONMENTAL CONSULTANTS LTD
APPENDIX A
ASBESTOS SURVEY - DATA RECORD SHEET - continued
Page 52
of 71
Opinions and interpretations expressed herein are outside the scope of UKAS accreditation held by VEGA
Report No: AR/04/1662
Date of survey: 13/10/04
Area ID
Surveyed
Location of sample point /
Level of
Sample
Extent
Product Condition
Surface
Asbestos
Score
Access
Action
Yes/No
Description
ID
ID
(m/m2/m3)
Type
(0,1,2,3)
Treatment
Type
(IA,OA,EA)
(A1,A2,A3)
of suspect material
(P/SP/ID)
(1,2,3)
(0,1,2,3)
(1,2,3)
GROUND
FLOOR (cont)
Bathroom 4
Yes
Ceiling – plasterboard
SP
-
-
-
-
-
NA
-
-
-
Walls – ceramic tiles over brick
SP
-
-
-
-
-
NA
-
-
-
Corner and low level boxing
SP
-
-
-
-
-
NA
-
-
-
Floor – vinyl over concrete
SP
-
-
-
-
-
NA
-
-
-
Toilet 13
Yes
Ceiling – plasterboard
SP
-
-
-
-
-
NA
-
-
-
Walls – ceramic tiles over brick
SP
-
-
-
-
-
NA
-
-
-
Toilet cistern
SP
-
-
-
-
-
NA
-
-
-
Corner boxing
SP
-
-
-
-
-
NA
-
-
-
Floor – vinyl over concrete
SP
-
-
-
-
-
NA
-
-
-
Level of ID: P – Presumed, SP – Strongly Presumed, ID – Identified.
Access: IA – Inaccessible, OA – Occasionally Accessed, EA – Easily/Regularly Accessed
Asbestos Type: NA – Non-Asbestos
Action: A1 – Remove ASAP, A2 – Repair/Encapsulate ASAP, A3 – Leave Undisturbed and Monitor Situation
Analyst – P Dean
Procedure ASB/6 APPENDIX B, Page 2 of 2, Issue No.5, Issue Date 23/01/03, Issued by VEGA
VEGA ENVIRONMENTAL CONSULTANTS LTD
APPENDIX A
ASBESTOS SURVEY - DATA RECORD SHEET - continued
Page 53
of 71
Opinions and interpretations expressed herein are outside the scope of UKAS accreditation held by VEGA
Report No: AR/04/1662
Date of survey: 13/10/04
Area ID
Surveyed
Location of sample point /
Level of
Sample
Extent
Product Condition
Surface
Asbestos
Score
Access
Action
Yes/No
Description
ID
ID
(m/m2/m3)
Type
(0,1,2,3)
Treatment
Type
(IA,OA,EA)
(A1,A2,A3)
of suspect material
(P/SP/ID)
(1,2,3)
(0,1,2,3)
(1,2,3)
GROUND
FLOOR (cont)
Toilet 14
Yes
Ceiling – plasterboard
SP
-
-
-
-
-
NA
-
-
-
Walls – ceramic tiles over brick
SP
-
-
-
-
-
NA
-
-
-
Toilet cistern
SP
-
-
-
-
-
NA
-
-
-
Corner boxing
SP
-
-
-
-
-
NA
-
-
-
Floor – vinyl over concrete
SP
-
-
-
-
-
NA
-
-
-
Store 7
Yes
Ceiling – plasterboard
SP
-
-
-
-
-
NA
-
-
-
Walls – plaster over brick
SP
-
-
-
-
-
NA
-
-
-
Electrical equipment
SP
-
-
-
-
-
NA
-
-
-
Floor – vinyl over concrete
SP
As
-
-
-
-
NA
-
-
-
BS/03
Level of ID: P – Presumed, SP – Strongly Presumed, ID – Identified.
Access: IA – Inaccessible, OA – Occasionally Accessed, EA – Easily/Regularly Accessed
Asbestos Type: NA – Non-Asbestos
Action: A1 – Remove ASAP, A2 – Repair/Encapsulate ASAP, A3 – Leave Undisturbed and Monitor Situation
Analyst – P Dean
Procedure ASB/6 APPENDIX B, Page 2 of 2, Issue No.5, Issue Date 23/01/03, Issued by VEGA
VEGA ENVIRONMENTAL CONSULTANTS LTD
APPENDIX A
ASBESTOS SURVEY - DATA RECORD SHEET - continued
Page 54
of 71
Opinions and interpretations expressed herein are outside the scope of UKAS accreditation held by VEGA
Report No: AR/04/1662
Date of survey: 13/10/04
Area ID
Surveyed
Location of sample point /
Level of
Sample
Extent
Product Condition
Surface
Asbestos
Score
Access
Action
Yes/No
Description
ID
ID
(m/m2/m3)
Type
(0,1,2,3)
Treatment
Type
(IA,OA,EA)
(A1,A2,A3)
of suspect material
(P/SP/ID)
(1,2,3)
(0,1,2,3)
(1,2,3)
GROUND
FLOOR (cont)
Bedroom 25
Yes
Ceiling – plasterboard
SP
-
-
-
-
-
NA
-
-
-
Walls – plaster over brick
SP
-
-
-
-
-
NA
-
-
-
Floor – carpet over concrete
SP
-
-
-
-
-
NA
-
-
-
Bedroom 26
Yes
Ceiling – plasterboard
SP
-
-
-
-
-
NA
-
-
-
Walls – plaster over brick
SP
-
-
-
-
-
NA
-
-
-
Floor – carpet over concrete
SP
-
-
-
-
-
NA
-
-
-
Bedroom 27
Yes
Ceiling – plasterboard
SP
-
-
-
-
-
NA
-
-
-
Walls – plaster over brick
SP
-
-
-
-
-
NA
-
-
-
Floor – carpet over concrete
SP
-
-
-
-
-
NA
-
-
-
Level of ID: P – Presumed, SP – Strongly Presumed, ID – Identified.
Access: IA – Inaccessible, OA – Occasionally Accessed, EA – Easily/Regularly Accessed
Asbestos Type: NA – Non-Asbestos
Action: A1 – Remove ASAP, A2 – Repair/Encapsulate ASAP, A3 – Leave Undisturbed and Monitor Situation
Analyst – P Dean
Procedure ASB/6 APPENDIX B, Page 2 of 2, Issue No.5, Issue Date 23/01/03, Issued by VEGA
VEGA ENVIRONMENTAL CONSULTANTS LTD
APPENDIX A
ASBESTOS SURVEY - DATA RECORD SHEET - continued
Page 55
of 71
Opinions and interpretations expressed herein are outside the scope of UKAS accreditation held by VEGA
Report No: AR/04/1662
Date of survey: 13/10/04
Area ID
Surveyed
Location of sample point /
Level of
Sample
Extent
Product Condition
Surface
Asbestos
Score
Access
Action
Yes/No
Description
ID
ID
(m/m2/m3)
Type
(0,1,2,3)
Treatment
Type
(IA,OA,EA)
(A1,A2,A3)
of suspect material
(P/SP/ID)
(1,2,3)
(0,1,2,3)
(1,2,3)
GROUND
FLOOR (cont)
Bedroom 28
Yes
Ceiling – plasterboard
SP
-
-
-
-
-
NA
-
-
-
Walls – plaster over brick
SP
-
-
-
-
-
NA
-
-
-
Floor – carpet over concrete
SP
-
-
-
-
-
NA
-
-
-
Kitchen 4
Yes
Ceiling – plasterboard
SP
-
-
-
-
-
NA
-
-
-
High level ceiling heater
SP
-
-
-
-
-
NA
-
-
-
Walls – ceramic tiles over brick
SP
-
-
-
-
-
NA
-
-
-
Door – window strip
SP
As
-
-
-
-
NA
-
-
-
BS/06
Hand basin – wood panel below
SP
-
-
-
-
-
NA
-
-
-
Floor – vinyl over concrete
SP
-
-
-
-
-
NA
-
-
-
Level of ID: P – Presumed, SP – Strongly Presumed, ID – Identified.
Access: IA – Inaccessible, OA – Occasionally Accessed, EA – Easily/Regularly Accessed
Asbestos Type: NA – Non-Asbestos
Action: A1 – Remove ASAP, A2 – Repair/Encapsulate ASAP, A3 – Leave Undisturbed and Monitor Situation
Analyst – P Dean
Procedure ASB/6 APPENDIX B, Page 2 of 2, Issue No.5, Issue Date 23/01/03, Issued by VEGA
VEGA ENVIRONMENTAL CONSULTANTS LTD
APPENDIX A
ASBESTOS SURVEY - DATA RECORD SHEET - continued
Page 56
of 71
Opinions and interpretations expressed herein are outside the scope of UKAS accreditation held by VEGA
Report No: AR/04/1662
Date of survey: 13/10/04
Area ID
Surveyed
Location of sample point /
Level of
Sample
Extent
Product Condition
Surface
Asbestos
Score
Access
Action
Yes/No
Description
ID
ID
(m/m2/m3)
Type
(0,1,2,3)
Treatment
Type
(IA,OA,EA)
(A1,A2,A3)
of suspect material
(P/SP/ID)
(1,2,3)
(0,1,2,3)
(1,2,3)
GROUND
FLOOR (cont)
Lounge 4
Yes
Ceiling – plasterboard
SP
-
-
-
-
-
NA
-
-
-
Walls – plaster over brick
SP
-
-
-
-
-
NA
-
-
-
Floor – carpet over concrete
SP
-
-
-
-
-
NA
-
-
-
Void above
Yes
Roof – internal loft insulation
SP
As
-
-
-
-
NA
-
-
-
Rooms adjacent
BS/02
Corridor 5
Walls – brick
SP
-
-
-
-
-
NA
-
-
-
Pipe insulation – MMMF
SP
-
-
-
-
-
NA
-
-
-
Loft insulation – MMMF
SP
-
-
-
-
-
NA
-
-
-
Water tank insulation –
SP
-
-
-
-
-
NA
-
-
-
polystyrene
Level of ID: P – Presumed, SP – Strongly Presumed, ID – Identified.
Access: IA – Inaccessible, OA – Occasionally Accessed, EA – Easily/Regularly Accessed
Asbestos Type: NA – Non-Asbestos
Action: A1 – Remove ASAP, A2 – Repair/Encapsulate ASAP, A3 – Leave Undisturbed and Monitor Situation
Analyst – P Dean
Procedure ASB/6 APPENDIX B, Page 2 of 2, Issue No.5, Issue Date 23/01/03, Issued by VEGA
VEGA ENVIRONMENTAL CONSULTANTS LTD
APPENDIX A
ASBESTOS SURVEY - DATA RECORD SHEET - continued
Page 57
of 71
Opinions and interpretations expressed herein are outside the scope of UKAS accreditation held by VEGA
Report No: AR/04/1662
Date of survey: 13/10/04
Area ID
Surveyed
Location of sample point /
Level of
Sample
Extent
Product Condition
Surface
Asbestos
Score
Access
Action
Yes/No
Description
ID
ID
(m/m2/m3)
Type
(0,1,2,3)
Treatment
Type
(IA,OA,EA)
(A1,A2,A3)
of suspect material
(P/SP/ID)
(1,2,3)
(0,1,2,3)
(1,2,3)
GROUND
FLOOR (cont)
Corridor 6
Yes
Ceiling – plasterboard
SP
-
-
-
-
-
NA
-
-
-
Walls – plaster over brick
SP
-
-
-
-
-
NA
-
-
-
Floor – carpet over concrete
SP
-
-
-
-
-
NA
-
-
-
Void above
Yes
Roof – internal loft insulation
SP
As
-
-
-
-
NA
-
-
-
BS/02
Walls – brick
SP
-
-
-
-
-
NA
-
-
-
Pipe insulation – MMMF
SP
-
-
-
-
-
NA
-
-
-
Loft insulation – MMMF
SP
-
-
-
-
-
NA
-
-
-
Water tank insulation –
SP
-
-
-
-
-
NA
-
-
-
polystyrene
Level of ID: P – Presumed, SP – Strongly Presumed, ID – Identified.
Access: IA – Inaccessible, OA – Occasionally Accessed, EA – Easily/Regularly Accessed
Asbestos Type: NA – Non-Asbestos
Action: A1 – Remove ASAP, A2 – Repair/Encapsulate ASAP, A3 – Leave Undisturbed and Monitor Situation
Analyst – P Dean
Procedure ASB/6 APPENDIX B, Page 2 of 2, Issue No.5, Issue Date 23/01/03, Issued by VEGA
VEGA ENVIRONMENTAL CONSULTANTS LTD
APPENDIX A
ASBESTOS SURVEY - DATA RECORD SHEET - continued
Page 58
of 71
Opinions and interpretations expressed herein are outside the scope of UKAS accreditation held by VEGA
Report No: AR/04/1662
Date of survey: 13/10/04
Area ID
Surveyed
Location of sample point /
Level of
Sample
Extent
Product Condition
Surface
Asbestos
Score
Access
Action
Yes/No
Description
ID
ID
(m/m2/m3)
Type
(0,1,2,3)
Treatment
Type
(IA,OA,EA)
(A1,A2,A3)
of suspect material
(P/SP/ID)
(1,2,3)
(0,1,2,3)
(1,2,3)
GROUND
FLOOR (cont)
Tank Room 6
Yes
Ceiling – plasterboard
SP
-
-
-
-
-
NA
-
-
-
Walls – plaster over brick
SP
-
-
-
-
-
NA
-
-
-
Pipe insulation – MMMF
SP
-
-
-
-
-
NA
-
-
-
Hot water tank insulation –
SP
-
-
-
-
-
NA
-
-
-
MMMF
Floor – vinyl over concrete
SP
As
-
-
-
-
NA
-
-
-
BS/03
Level of ID: P – Presumed, SP – Strongly Presumed, ID – Identified.
Access: IA – Inaccessible, OA – Occasionally Accessed, EA – Easily/Regularly Accessed
Asbestos Type: NA – Non-Asbestos
Action: A1 – Remove ASAP, A2 – Repair/Encapsulate ASAP, A3 – Leave Undisturbed and Monitor Situation
Analyst – P Dean
Procedure ASB/6 APPENDIX B, Page 2 of 2, Issue No.5, Issue Date 23/01/03, Issued by VEGA
VEGA ENVIRONMENTAL CONSULTANTS LTD
APPENDIX A
ASBESTOS SURVEY - DATA RECORD SHEET - continued
Page 59
of 71
Opinions and interpretations expressed herein are outside the scope of UKAS accreditation held by VEGA
Report No: AR/04/1662
Date of survey: 13/10/04
Area ID
Surveyed
Location of sample point /
Level of
Sample
Extent
Product Condition
Surface
Asbestos
Score
Access
Action
Yes/No
Description
ID
ID
(m/m2/m3)
Type
(0,1,2,3)
Treatment
Type
(IA,OA,EA)
(A1,A2,A3)
of suspect material
(P/SP/ID)
(1,2,3)
(0,1,2,3)
(1,2,3)
GROUND
FLOOR (cont)
Toilet 15
Yes
Ceiling – plasterboard
SP
-
-
-
-
-
NA
-
-
-
Walls – ceramic tiles over brick
SP
-
-
-
-
-
NA
-
-
-
Toilet cistern
SP
-
-
-
-
-
NA
-
-
-
Corner boxing
SP
-
-
-
-
-
NA
-
-
-
Floor – vinyl over concrete
SP
-
-
-
-
-
NA
-
-
-
First Aid Point
Yes
Ceiling – plasterboard
SP
-
-
-
-
-
NA
-
-
-
2
Walls – plaster over brick
SP
-
-
-
-
-
NA
-
-
-
Electrical equipment
SP
-
-
-
-
-
NA
-
-
-
Ironing board – heat plate
SP
As
-
-
-
-
NA
-
-
-
BS/06
Level of ID: P – Presumed, SP – Strongly Presumed, ID – Identified.
Access: IA – Inaccessible, OA – Occasionally Accessed, EA – Easily/Regularly Accessed
Asbestos Type: NA – Non-Asbestos
Action: A1 – Remove ASAP, A2 – Repair/Encapsulate ASAP, A3 – Leave Undisturbed and Monitor Situation
Analyst – P Dean
Procedure ASB/6 APPENDIX B, Page 2 of 2, Issue No.5, Issue Date 23/01/03, Issued by VEGA
VEGA ENVIRONMENTAL CONSULTANTS LTD
APPENDIX A
ASBESTOS SURVEY - DATA RECORD SHEET - continued
Page 60
of 71
Opinions and interpretations expressed herein are outside the scope of UKAS accreditation held by VEGA
Report No: AR/04/1662
Date of survey: 13/10/04
Area ID
Surveyed
Location of sample point /
Level of
Sample
Extent
Product Condition
Surface
Asbestos
Score
Access
Action
Yes/No
Description
ID
ID
(m/m2/m3)
Type
(0,1,2,3)
Treatment
Type
(IA,OA,EA)
(A1,A2,A3)
of suspect material
(P/SP/ID)
(1,2,3)
(0,1,2,3)
(1,2,3)
GROUND
FLOOR (cont)
First Aid Point
Yes
Floor – vinyl over concrete
SP
As
-
-
-
-
NA
-
-
-
2 (cont)
BS/03
Store 8
Yes
Ceiling – plasterboard
SP
-
-
-
-
-
NA
-
-
-
Walls – plaster over brick
SP
-
-
-
-
-
NA
-
-
-
Electrical equipment
SP
-
-
-
-
-
NA
-
-
-
Floor – vinyl over concrete
SP
As
-
-
-
-
NA
-
-
-
BS/03
Sluice Room 4
Yes
Ceiling – plasterboard
SP
-
-
-
-
-
NA
-
-
-
Walls – plaster over brick
SP
-
-
-
-
-
NA
-
-
-
Toilet cisterns
SP
-
-
-
-
-
NA
-
-
-
Floor – vinyl over concrete
SP
-
-
-
-
-
NA
-
-
-
Level of ID: P – Presumed, SP – Strongly Presumed, ID – Identified.
Access: IA – Inaccessible, OA – Occasionally Accessed, EA – Easily/Regularly Accessed
Asbestos Type: NA – Non-Asbestos
Action: A1 – Remove ASAP, A2 – Repair/Encapsulate ASAP, A3 – Leave Undisturbed and Monitor Situation
Analyst – P Dean
Procedure ASB/6 APPENDIX B, Page 2 of 2, Issue No.5, Issue Date 23/01/03, Issued by VEGA
VEGA ENVIRONMENTAL CONSULTANTS LTD
APPENDIX A
ASBESTOS SURVEY - DATA RECORD SHEET - continued
Page 61
of 71
Opinions and interpretations expressed herein are outside the scope of UKAS accreditation held by VEGA
Report No: AR/04/1662
Date of survey: 13/10/04
Area ID
Surveyed
Location of sample point /
Level of
Sample
Extent
Product Condition
Surface
Asbestos
Score
Access
Action
Yes/No
Description
ID
ID
(m/m2/m3)
Type
(0,1,2,3)
Treatment
Type
(IA,OA,EA)
(A1,A2,A3)
of suspect material
(P/SP/ID)
(1,2,3)
(0,1,2,3)
(1,2,3)
GROUND
FLOOR (cont)
Dining Room 4
Yes
Ceiling – textured coating
ID
BS/08
-
-
-
-
NA
-
-
-
Walls – plaster over brick
SP
-
-
-
-
-
NA
-
-
-
Floor – carpet over concrete
SP
-
-
-
-
-
NA
-
-
-
Kitchen 5
Yes
Ceiling – plasterboard
SP
-
-
-
-
-
NA
-
-
-
High level ceiling heater
SP
-
-
-
-
-
NA
-
-
-
Walls – ceramic tiles over brick
SP
-
-
-
-
-
NA
-
-
-
Door – window strip
SP
As
-
-
-
-
NA
-
-
-
BS/06
Hand basin – wood panel below
SP
-
-
-
-
-
NA
-
-
-
Floor – vinyl over concrete
SP
-
-
-
-
-
NA
-
-
-
Level of ID: P – Presumed, SP – Strongly Presumed, ID – Identified.
Access: IA – Inaccessible, OA – Occasionally Accessed, EA – Easily/Regularly Accessed
Asbestos Type: NA – Non-Asbestos
Action: A1 – Remove ASAP, A2 – Repair/Encapsulate ASAP, A3 – Leave Undisturbed and Monitor Situation
Analyst – P Dean
Procedure ASB/6 APPENDIX B, Page 2 of 2, Issue No.5, Issue Date 23/01/03, Issued by VEGA
VEGA ENVIRONMENTAL CONSULTANTS LTD
APPENDIX A
ASBESTOS SURVEY - DATA RECORD SHEET - continued
Page 62
of 71
Opinions and interpretations expressed herein are outside the scope of UKAS accreditation held by VEGA
Report No: AR/04/1662
Date of survey: 13/10/04
Area ID
Surveyed
Location of sample point /
Level of
Sample
Extent
Product Condition
Surface
Asbestos
Score
Access
Action
Yes/No
Description
ID
ID
(m/m2/m3)
Type
(0,1,2,3)
Treatment
Type
(IA,OA,EA)
(A1,A2,A3)
of suspect material
(P/SP/ID)
(1,2,3)
(0,1,2,3)
(1,2,3)
GROUND
FLOOR (cont)
Bedroom 29
Yes
Ceiling – plasterboard
SP
-
-
-
-
-
NA
-
-
-
Walls – plaster over brick
SP
-
-
-
-
-
NA
-
-
-
Floor – carpet over concrete
SP
-
-
-
-
-
NA
-
-
-
Bedroom 30
Yes
Ceiling – plasterboard
SP
-
-
-
-
-
NA
-
-
-
Walls – plaster over brick
SP
-
-
-
-
-
NA
-
-
-
Floor – carpet over concrete
SP
-
-
-
-
-
NA
-
-
-
Bedroom 31
Yes
Ceiling – plasterboard
SP
-
-
-
-
-
NA
-
-
-
Walls – plaster over brick
SP
-
-
-
-
-
NA
-
-
-
Floor – carpet over concrete
SP
-
-
-
-
-
NA
-
-
-
Level of ID: P – Presumed, SP – Strongly Presumed, ID – Identified.
Access: IA – Inaccessible, OA – Occasionally Accessed, EA – Easily/Regularly Accessed
Asbestos Type: NA – Non-Asbestos
Action: A1 – Remove ASAP, A2 – Repair/Encapsulate ASAP, A3 – Leave Undisturbed and Monitor Situation
Analyst – P Dean
Procedure ASB/6 APPENDIX B, Page 2 of 2, Issue No.5, Issue Date 23/01/03, Issued by VEGA
VEGA ENVIRONMENTAL CONSULTANTS LTD
APPENDIX A
ASBESTOS SURVEY - DATA RECORD SHEET - continued
Page 63
of 71
Opinions and interpretations expressed herein are outside the scope of UKAS accreditation held by VEGA
Report No: AR/04/1662
Date of survey: 13/10/04
Area ID
Surveyed
Location of sample point /
Level of
Sample
Extent
Product Condition
Surface
Asbestos
Score
Access
Action
Yes/No
Description
ID
ID
(m/m2/m3)
Type
(0,1,2,3)
Treatment
Type
(IA,OA,EA)
(A1,A2,A3)
of suspect material
(P/SP/ID)
(1,2,3)
(0,1,2,3)
(1,2,3)
GROUND
FLOOR (cont)
Bedroom 32
Yes
Ceiling – plasterboard
SP
-
-
-
-
-
NA
-
-
-
Walls – plaster over brick
SP
-
-
-
-
-
NA
-
-
-
Floor – carpet over concrete
SP
-
-
-
-
-
NA
-
-
-
Bedroom 33
Yes
Ceiling – plasterboard
SP
-
-
-
-
-
NA
-
-
-
Walls – plaster over brick
SP
-
-
-
-
-
NA
-
-
-
Floor – carpet over concrete
SP
-
-
-
-
-
NA
-
-
-
Bedroom 34
Yes
Ceiling – plasterboard
SP
-
-
-
-
-
NA
-
-
-
Walls – plaster over brick
SP
-
-
-
-
-
NA
-
-
-
Floor – carpet over concrete
SP
-
-
-
-
-
NA
-
-
-
Level of ID: P – Presumed, SP – Strongly Presumed, ID – Identified.
Access: IA – Inaccessible, OA – Occasionally Accessed, EA – Easily/Regularly Accessed
Asbestos Type: NA – Non-Asbestos
Action: A1 – Remove ASAP, A2 – Repair/Encapsulate ASAP, A3 – Leave Undisturbed and Monitor Situation
Analyst – P Dean
Procedure ASB/6 APPENDIX B, Page 2 of 2, Issue No.5, Issue Date 23/01/03, Issued by VEGA
VEGA ENVIRONMENTAL CONSULTANTS LTD
APPENDIX A
ASBESTOS SURVEY - DATA RECORD SHEET - continued
Page 64
of 71
Opinions and interpretations expressed herein are outside the scope of UKAS accreditation held by VEGA
Report No: AR/04/1662
Date of survey: 13/10/04
Area ID
Surveyed
Location of sample point /
Level of
Sample
Extent
Product Condition
Surface
Asbestos
Score
Access
Action
Yes/No
Description
ID
ID
(m/m2/m3)
Type
(0,1,2,3)
Treatment
Type
(IA,OA,EA)
(A1,A2,A3)
of suspect material
(P/SP/ID)
(1,2,3)
(0,1,2,3)
(1,2,3)
GROUND
FLOOR (cont)
Bedroom 35
Yes
Ceiling – plasterboard
SP
-
-
-
-
-
NA
-
-
-
Walls – plaster over brick
SP
-
-
-
-
-
NA
-
-
-
Floor – carpet over concrete
SP
-
-
-
-
-
NA
-
-
-
Bedroom 36
Yes
Ceiling – plasterboard
SP
-
-
-
-
-
NA
-
-
-
Walls – plaster over brick
SP
-
-
-
-
-
NA
-
-
-
Floor – carpet over concrete
SP
-
-
-
-
-
NA
-
-
-
Bathroom 5
Yes
Ceiling – plasterboard
SP
-
-
-
-
-
NA
-
-
-
Walls – ceramic tiles over brick
SP
-
-
-
-
-
NA
-
-
-
Corner and low level boxing
SP
-
-
-
-
-
NA
-
-
-
Floor – vinyl over concrete
SP
-
-
-
-
-
NA
-
-
-
Level of ID: P – Presumed, SP – Strongly Presumed, ID – Identified.
Access: IA – Inaccessible, OA – Occasionally Accessed, EA – Easily/Regularly Accessed
Asbestos Type: NA – Non-Asbestos
Action: A1 – Remove ASAP, A2 – Repair/Encapsulate ASAP, A3 – Leave Undisturbed and Monitor Situation
Analyst – P Dean
Procedure ASB/6 APPENDIX B, Page 2 of 2, Issue No.5, Issue Date 23/01/03, Issued by VEGA
VEGA ENVIRONMENTAL CONSULTANTS LTD
APPENDIX A
ASBESTOS SURVEY - DATA RECORD SHEET - continued
Page 65
of 71
Opinions and interpretations expressed herein are outside the scope of UKAS accreditation held by VEGA
Report No: AR/04/1662
Date of survey: 13/10/04
Area ID
Surveyed
Location of sample point /
Level of
Sample
Extent
Product Condition
Surface
Asbestos
Score
Access
Action
Yes/No
Description
ID
ID
(m/m2/m3)
Type
(0,1,2,3)
Treatment
Type
(IA,OA,EA)
(A1,A2,A3)
of suspect material
(P/SP/ID)
(1,2,3)
(0,1,2,3)
(1,2,3)
GROUND
FLOOR (cont)
Toilet 16
Yes
Ceiling – plasterboard
SP
-
-
-
-
-
NA
-
-
-
Walls – ceramic tiles over brick
SP
-
-
-
-
-
NA
-
-
-
Toilet cistern
SP
-
-
-
-
-
NA
-
-
-
Corner boxing
SP
-
-
-
-
-
NA
-
-
-
Floor – vinyl over concrete
SP
-
-
-
-
-
NA
-
-
-
Level of ID: P – Presumed, SP – Strongly Presumed, ID – Identified.
Access: IA – Inaccessible, OA – Occasionally Accessed, EA – Easily/Regularly Accessed
Asbestos Type: NA – Non-Asbestos
Action: A1 – Remove ASAP, A2 – Repair/Encapsulate ASAP, A3 – Leave Undisturbed and Monitor Situation
Analyst – P Dean
Procedure ASB/6 APPENDIX B, Page 2 of 2, Issue No.5, Issue Date 23/01/03, Issued by VEGA
VEGA ENVIRONMENTAL CONSULTANTS LTD
APPENDIX A
ASBESTOS SURVEY - DATA RECORD SHEET - continued
Page 66
of 71
Opinions and interpretations expressed herein are outside the scope of UKAS accreditation held by VEGA
Report No: AR/04/1662
Date of survey: 13/10/04
Area ID
Surveyed
Location of sample point /
Level of
Sample
Extent
Product Condition
Surface
Asbestos
Score
Access
Action
Yes/No
Description
ID
ID
(m/m2/m3)
Type
(0,1,2,3)
Treatment
Type
(IA,OA,EA)
(A1,A2,A3)
of suspect material
(P/SP/ID)
(1,2,3)
(0,1,2,3)
(1,2,3)
GROUND
FLOOR (cont)
Toilet 17
Yes
Ceiling – plasterboard
SP
-
-
-
-
-
NA
-
-
-
Walls – ceramic tiles over brick
SP
-
-
-
-
-
NA
-
-
-
Toilet cistern
SP
-
-
-
-
-
NA
-
-
-
Corner boxing
SP
-
-
-
-
-
NA
-
-
-
Floor – vinyl over concrete
SP
-
-
-
-
-
NA
-
-
-
Level of ID: P – Presumed, SP – Strongly Presumed, ID – Identified.
Access: IA – Inaccessible, OA – Occasionally Accessed, EA – Easily/Regularly Accessed
Asbestos Type: NA – Non-Asbestos
Action: A1 – Remove ASAP, A2 – Repair/Encapsulate ASAP, A3 – Leave Undisturbed and Monitor Situation
Analyst – P Dean
Procedure ASB/6 APPENDIX B, Page 2 of 2, Issue No.5, Issue Date 23/01/03, Issued by VEGA
VEGA ENVIRONMENTAL CONSULTANTS LTD
APPENDIX A
ASBESTOS SURVEY - DATA RECORD SHEET - continued
Page 67
of 71
Opinions and interpretations expressed herein are outside the scope of UKAS accreditation held by VEGA
Report No: AR/04/1662
Date of survey: 13/10/04
Area ID
Surveyed
Location of sample point /
Level of
Sample
Extent
Product Condition
Surface
Asbestos
Score
Access
Action
Yes/No
Description
ID
ID
(m/m2/m3)
Type
(0,1,2,3)
Treatment
Type
(IA,OA,EA)
(A1,A2,A3)
of suspect material
(P/SP/ID)
(1,2,3)
(0,1,2,3)
(1,2,3)
GROUND
FLOOR (cont)
Lounge 5
Yes
Ceiling – plasterboard
SP
-
-
-
-
-
NA
-
-
-
Walls – plaster over brick
SP
-
-
-
-
-
NA
-
-
-
Floor – carpet over concrete
SP
-
-
-
-
-
NA
-
-
-
Void above
Yes
Roof – internal loft insulation
SP
As
-
-
-
-
NA
-
-
-
Rooms adjacent
BS/02
Corridor 6
Walls – brick
SP
-
-
-
-
-
NA
-
-
-
Pipe insulation – MMMF
SP
-
-
-
-
-
NA
-
-
-
Loft insulation – MMMF
SP
-
-
-
-
-
NA
-
-
-
Water tank insulation –
SP
-
-
-
-
-
NA
-
-
-
polystyrene
Level of ID: P – Presumed, SP – Strongly Presumed, ID – Identified.
Access: IA – Inaccessible, OA – Occasionally Accessed, EA – Easily/Regularly Accessed
Asbestos Type: NA – Non-Asbestos
Action: A1 – Remove ASAP, A2 – Repair/Encapsulate ASAP, A3 – Leave Undisturbed and Monitor Situation
Analyst – P Dean
Procedure ASB/6 APPENDIX B, Page 2 of 2, Issue No.5, Issue Date 23/01/03, Issued by VEGA
VEGA ENVIRONMENTAL CONSULTANTS LTD
APPENDIX A
ASBESTOS SURVEY - DATA RECORD SHEET - continued
Page 68
of 71
Opinions and interpretations expressed herein are outside the scope of UKAS accreditation held by VEGA
Report No: AR/04/1662
Date of survey: 13/10/04
Area ID
Surveyed
Location of sample point /
Level of
Sample
Extent
Product Condition
Surface
Asbestos
Score
Access
Action
Yes/No
Description
ID
ID
(m/m2/m3)
Type
(0,1,2,3)
Treatment
Type
(IA,OA,EA)
(A1,A2,A3)
of suspect material
(P/SP/ID)
(1,2,3)
(0,1,2,3)
(1,2,3)
GROUND
FLOOR (cont)
Boiler Room
Yes
Ceiling – plasterboard
SP
-
-
-
-
-
NA
-
-
-
Walls – brick
SP
-
-
-
-
-
NA
-
-
-
Pipe insulation – MMMF
SP
-
-
-
-
-
NA
-
-
-
Boilers x 3 – internal MMMF
SP
-
-
-
-
-
NA
-
-
-
insulation
Boiler burner insulation x 3
ID
BS/09
-
-
-
-
NA
-
-
-
Boiler flue pipes x 3
SP
-
-
-
-
-
NA
-
-
-
Flange gaskets – various
SP
As
1m²
1
0
0
1
2
OA
A3
locations
BS/04
Tank – polystyrene insulation
SP
-
-
-
-
-
NA
-
-
-
Hot water tank – MMMF
SP
-
-
-
-
-
NA
-
-
-
insulation
Floor – concrete
SP
-
-
-
-
-
NA
-
-
-
Level of ID: P – Presumed, SP – Strongly Presumed, ID – Identified.
Access: IA – Inaccessible, OA – Occasionally Accessed, EA – Easily/Regularly Accessed
Asbestos Type: NA – Non-Asbestos
Action: A1 – Remove ASAP, A2 – Repair/Encapsulate ASAP, A3 – Leave Undisturbed and Monitor Situation
Analyst – P Dean
Procedure ASB/6 APPENDIX B, Page 2 of 2, Issue No.5, Issue Date 23/01/03, Issued by VEGA
VEGA ENVIRONMENTAL CONSULTANTS LTD
APPENDIX A
ASBESTOS SURVEY - DATA RECORD SHEET - continued
Page 69
of 71
Opinions and interpretations expressed herein are outside the scope of UKAS accreditation held by VEGA
Report No: AR/04/1662
Date of survey: 13/10/04
Area ID
Surveyed
Location of sample point /
Level of
Sample
Extent
Product Condition
Surface
Asbestos
Score
Access
Action
Yes/No
Description
ID
ID
(m/m2/m3)
Type
(0,1,2,3)
Treatment
Type
(IA,OA,EA)
(A1,A2,A3)
of suspect material
(P/SP/ID)
(1,2,3)
(0,1,2,3)
(1,2,3)
GROUND
FLOOR (cont)
Generator
Yes
Ceiling – plasterboard
SP
-
-
-
-
-
NA
-
-
-
Room
Walls – brick
SP
-
-
-
-
-
NA
-
-
-
Generator exhaust – insulation
ID
BS/10
-
-
-
-
NA
-
-
-
Pipe insulation – MMMF
SP
-
-
-
-
-
NA
-
-
-
Floor – concrete
SP
-
-
-
-
-
NA
-
-
-
Level of ID: P – Presumed, SP – Strongly Presumed, ID – Identified.
Access: IA – Inaccessible, OA – Occasionally Accessed, EA – Easily/Regularly Accessed
Asbestos Type: NA – Non-Asbestos
Action: A1 – Remove ASAP, A2 – Repair/Encapsulate ASAP, A3 – Leave Undisturbed and Monitor Situation
Analyst – P Dean
Procedure ASB/6 APPENDIX B, Page 2 of 2, Issue No.5, Issue Date 23/01/03, Issued by VEGA
VEGA ENVIRONMENTAL CONSULTANTS LTD
APPENDIX A
ASBESTOS SURVEY - DATA RECORD SHEET - continued
Page 70
of 71
Opinions and interpretations expressed herein are outside the scope of UKAS accreditation held by VEGA
Report No: AR/04/1662
Date of survey: 13/10/04
Area ID
Surveyed
Location of sample point /
Level of
Sample
Extent
Product Condition
Surface
Asbestos
Score
Access
Action
Yes/No
Description
ID
ID
(m/m2/m3)
Type
(0,1,2,3)
Treatment
Type
(IA,OA,EA)
(A1,A2,A3)
of suspect material
(P/SP/ID)
(1,2,3)
(0,1,2,3)
(1,2,3)
EXTERIOR
Main Building
Yes
Roof – tiles
SP
-
-
-
-
-
NA
-
-
-
Verge boards – plastic
SP
-
-
-
-
-
NA
-
-
-
Fascias and soffits – wood
SP
-
-
-
-
-
NA
-
-
-
Walls – brick
SP
-
-
-
-
-
NA
-
-
-
Gutters and down pipes – plastic
SP
-
-
-
-
-
NA
-
-
-
Damp proof course
SP
-
-
-
-
-
NA
-
-
-
Garage
Yes
Roof – internal felt
SP
As
-
-
-
-
NA
-
-
-
BS/02
Walls - brick
SP
-
-
-
-
-
NA
-
-
-
Floor – concrete
SP
-
-
-
-
-
NA
-
-
-
Level of ID: P – Presumed, SP – Strongly Presumed, ID – Identified.
Access: IA – Inaccessible, OA – Occasionally Accessed, EA – Easily/Regularly Accessed
Asbestos Type: NA – Non-Asbestos
Action: A1 – Remove ASAP, A2 – Repair/Encapsulate ASAP, A3 – Leave Undisturbed and Monitor Situation
Analyst – P Dean
Procedure ASB/6 APPENDIX B, Page 2 of 2, Issue No.5, Issue Date 23/01/03, Issued by VEGA
VEGA ENVIRONMENTAL CONSULTANTS LTD
APPENDIX A
ASBESTOS SURVEY - DATA RECORD SHEET - continued
Page 71
of 71
Opinions and interpretations expressed herein are outside the scope of UKAS accreditation held by VEGA
Report No: AR/04/1662
Date of survey: 13/10/04
Area ID
Surveyed
Location of sample point /
Level of
Sample
Extent
Product Condition
Surface
Asbestos
Score
Access
Action
Yes/No
Description
ID
ID
(m/m2/m3)
Type
(0,1,2,3)
Treatment
Type
(IA,OA,EA)
(A1,A2,A3)
of suspect material
(P/SP/ID)
(1,2,3)
(0,1,2,3)
(1,2,3)
EXTERIOR
(cont)
Garage Exterior
Yes
Roof – tiles
SP
-
-
-
-
-
NA
-
-
-
Verge boards – plastic
SP
-
-
-
-
-
NA
-
-
-
Fascias and soffits – wood
SP
-
-
-
-
-
NA
-
-
-
Walls – brick
SP
-
-
-
-
-
NA
-
-
-
Gutters and down pipes – plastic
SP
-
-
-
-
-
NA
-
-
-
Damp proof course
SP
-
-
-
-
-
NA
-
-
-
Level of ID: P – Presumed, SP – Strongly Presumed, ID – Identified.
Access: IA – Inaccessible, OA – Occasionally Accessed, EA – Easily/Regularly Accessed
Asbestos Type: NA – Non-Asbestos
Action: A1 – Remove ASAP, A2 – Repair/Encapsulate ASAP, A3 – Leave Undisturbed and Monitor Situation
Analyst – P Dean
Procedure ASB/6 APPENDIX B, Page 2 of 2, Issue No.5, Issue Date 23/01/03, Issued by VEGA
APPENDIX B
VEGA ENVIRONMENTAL CONSULTANTS LTD
MATERIAL ASSESSMENT ALGORITHM – FOR TYPE 1/TYPE 2 SURVEY
Sample Variable
Score
Main Examples
Product Type
1
Asbestos reinforced composites (plastic, resins, mastics, roofing
felts, vinyl floor tiles, semi-rigid paints or decorative finishes,
asbestos cement etc.)
2
Asbestos insulating board, mill boards, other low-density insulation
boards, asbestos textiles, gaskets, ropes and woven textiles,
asbestos paper and felt.
3
Thermal insulation (e.g. pipe and boiler lagging), sprayed asbestos,
loose asbestos, asbestos mattresses and packing.
Condition
0
Good condition: no visible damage
1
Low damage: a few scratches or surface marks; broken edges on
boards, tiles etc.
2
Medium damage: significant breakage of materials or several small
areas where material has been damaged revealing loose asbestos
fibres.
3
High damage or delamination of materials, sprays and thermal
insulation. Visible asbestos debris.
Surface Treatment
0
Composite materials containing asbestos: reinforced plastics,
resins, vinyl tiles, painted or asbestos cement (with exposed face
painted or encapsulated)
1
Enclosed sprays and lagging, AIB (with exposed face painted or
encapsulated), asbestos cement sheets etc.
2
Unsealed AIB, or encapsulated lagging and sprays.
3
Unsealed lagging and sprays.
Asbestos Type
1
Chrysotile.
2
Amphibole asbestos excluding crocidolite.
3
Crocidolite.
INITIAL ACTION PLAN
MATERIAL ASSESSMENT
ACCESS
SCORE
Inaccessible
Occasionally Easily/Regularly
Accessed
Accessed
Very Low Risk: < 5
A3
A3
A3
Low Risk: 5-6
A3
A3
A2
Medium Risk: 7-9
A3
A2
A1
High Risk: 10-12
A2
A1
A1
Procedure ASB/6 APPENDIX C, Page 1 of 1, Issue No. 2, Issue Date 26/01/04, Issued by VEGA
CONFIDENTIAL
APPENDIX C
ASBESTOS ANALYSIS REPORT
Page 1
of 2
Report No: AR/04/1662
Date of Issue:
26/10/04
Client: Mr R Brown
Date Sample Received:
13/10/04
Northumberland County Council
Date Analysed:
22/10/04
Laboratory:
Permanent
Order/Contract No. -
Origin of bulk sample:
Tynedale House, Aged Persons Home, Cowpen, Blyth,
Northumberland
Samples taken by:
P Dean
Company:
Vega Ltd
Samples analysed by
H J Curry
Sample ID
Location of Sample Point
Analysis
BS/01
Ground Floor, Reception Area, No asbestos detected
Ceiling – textured coating
BS/02
Ground Floor, Void above
No asbestos detected
Corridor 1, Roof – internal loft
insulation
BS/03
Ground Floor, Vegetable Store, No asbestos detected
Floor – vinyl covering
Analysis was carried out in accordance with MDHS 77: June 1994 by documented in-house procedure
Number ASB/3. VEGA cannot accept responsibility for the information on, or condition of, bulk samples taken/supplied
by non-Vega personnel or the effect such information or condition may have on the analysis of fibrous
content.
Checked By: __________________
Authorised By: _________________
Procedure ASB/3 APPENDIX B, Page 1 of 2, Issue No.8, Issue Date 22/01/03, Issued by VEGA
CONFIDENTIAL
APPENDIX C
ASBESTOS ANALYSIS REPORT - CONTINUED
Page 2
of 2
Report No. AR/04/1662
Sample ID
Location of Sample Point
Analysis
BS/04
Ground Floor, Laundry, Gas
Chrysotile – (white asbestos)
Pipe – flange gasket
BS/05
Ground Floor, Dining Room 1, No asbestos detected
Ceiling – textured coating
BS/06
Ground Floor, Kitchen 1, Door No asbestos detected
– window strip
BS/07
Ground Floor, Dining Room 3, No asbestos detected
Ceiling – textured coating
BS/08
Ground Floor, Dining Room 4, No asbestos detected
Ceiling – textured coating
BS/09
Ground Floor, Boiler Room,
No asbestos detected
Boilers – burner insulation
BS/10
Ground Floor, Generator
No asbestos detected
Room, Generator Exhaust –
insulation
Analysis was carried out in accordance with MDHS 77: June 1994 by documented in-house procedure
Number ASB/3. VEGA cannot accept responsibility for the information on, or condition of, bulk samples taken/supplied
by non-Vega personnel or the effect such information or condition may have on the analysis of fibrous
content.
Procedure ASB/3 APPENDIX B, Page 2 of 2, Issue No. 8, Issue Date 22/01/03, Issued by VEGA