Asbestos Material & Priority Assessment
Report
at
CAMHS/Lodge Road TAJ51
Survey Conducted by: Riverside Environmental Services Ltd
Date: 8/12/2016
Survey Report Number J099844 Sandwell New Code
CAMHS/Lodge Road TAJ51
Sample Record Number: J054909PS69
Building External Element Position Location :Gasket
Inspection Date
14/9/2016
Component:
Gaskets
Sample No.
J054909PS69
Survey Type
Type 2
Surveyor
Richard Farmer
Asbestos type
Chrysotile
Quantity of Material
10Nº
Material Assessment Material
2 Extent of Damage
0
Surface Treatment
1 Asbestos Type
1
Material Assessment Total:
4 C
Comments: This material requires no immediate
attention.
Priority Assessment Main Type of Activity
0 Extent of Material
0
Maintenance Activity
0 Location
2
Accessibility
0 Number of Occupants
0
Frequency of use
0 Average time is in use
0
Frequency of maintenance activity
1
Risk Assessment Total:
2
Total Score:
6 Sound
Actions Arising
Due Date
Est. Cost
Label & Manage
9-11-2016
£0
Re-Inspection Schedule:
Status
Due Date
Due after six Months
14-9-2017
CAMHS/Lodge Road TAJ51
Sample Record Number: FU000410
Basement -1, Plant Room 007-03-(-1)-001 Position Location :Flash Guard
Inspection Date
14/9/2016
Component:
Flash Guard
Sample No.
FU000410
Survey Type
Type 2
Surveyor
Richard Farmer
Asbestos type
Chrysotile
Quantity of Material
2Nº
Material Assessment Material
2 Extent of Damage
2
Surface Treatment
2 Asbestos Type
1
Material Assessment Total:
7 B
Comments: Restrict access and remove the material as soon as
is practicable.
Priority Assessment Main Type of Activity
0 Extent of Material
0
Maintenance Activity
0 Location
2
Accessibility
0 Number of Occupants
0
Frequency of use
0 Average time is in use
0
Frequency of maintenance activity
0
Risk Assessment Total:
1
Total Score:
8 Slight Risk
Actions Arising
Due Date
Est. Cost
Re-Inspection Schedule:
Status
Due Date
Due after six Months
14-9-2017
CAMHS/Lodge Road TAJ51
Sample Record Number: FU000411
Basement -1, Plant Room 007-03-(-1)-001 Position Location :Walls
Inspection Date
14/9/2016
Component:
Residue
Sample No.
FU000411
Survey Type
Type 2
Surveyor
Richard Farmer
Asbestos type
Chrysotile
Quantity of Material
10m²
Material Assessment Material
3 Extent of Damage
3
Surface Treatment
3 Asbestos Type
1
Material Assessment Total:
10 A
Comments: Restrict access and remove the material as soon as
possible.
Priority Assessment Main Type of Activity
0 Extent of Material
2
Maintenance Activity
0 Location
2
Accessibility
0 Number of Occupants
0
Frequency of use
0 Average time is in use
0
Frequency of maintenance activity
1
Risk Assessment Total:
2
Total Score:
12 Slight Risk
Actions Arising
Due Date
Est. Cost
Remove under Controlled Conditions by Approved
Contractor.
9-11-2016
£0
Re-Inspection Schedule:
Status
Due Date
Due after six Months
14-9-2017
CAMHS/Lodge Road TAJ51
Sample Record Number: FU000412
Basement -1, Plant Room 007-03-(-1)-001 Position Location :Behind Pipework
Inspection Date
14/9/2016
Component:
Residue
Sample No.
FU000412
Survey Type
Type 2
Surveyor
Richard Farmer
Asbestos type
Chrysotile
Quantity of Material
8lm
Material Assessment Material
3 Extent of Damage
3
Surface Treatment
2 Asbestos Type
1
Material Assessment Total:
9 B
Comments: Restrict access and remove material as soon as
possible.
Priority Assessment Main Type of Activity
0 Extent of Material
1
Maintenance Activity
0 Location
2
Accessibility
0 Number of Occupants
0
Frequency of use
0 Average time is in use
0
Frequency of maintenance activity
1
Risk Assessment Total:
2
Total Score:
11 Slight Risk
Actions Arising
Due Date
Est. Cost
Remove under Controlled Conditions by Approved
Contractor.
9-11-2016
£0
Re-Inspection Schedule:
Status
Due Date
Due after six Months
14-9-2017
CAMHS/Lodge Road TAJ51
Sample Record Number: FU000413
Basement -1, Plant Room 007-03-(-1)-001 Position Location :Wall
Inspection Date
14/9/2016
Component:
Residue
Sample No.
FU000413
Survey Type
Type 2
Surveyor
Richard Farmer
Asbestos type
Chrysotile
Quantity of Material
10m²
Material Assessment Material
3 Extent of Damage
3
Surface Treatment
2 Asbestos Type
1
Material Assessment Total:
9 B
Comments: Restrict access and remove material as soon as
possible.
Priority Assessment Main Type of Activity
0 Extent of Material
1
Maintenance Activity
0 Location
2
Accessibility
0 Number of Occupants
0
Frequency of use
0 Average time is in use
0
Frequency of maintenance activity
1
Risk Assessment Total:
2
Total Score:
11 Slight Risk
Actions Arising
Due Date
Est. Cost
Remove under Controlled Conditions by Approved
Contractor.
9-11-2016
£0
Re-Inspection Schedule:
Status
Due Date
Due after six Months
14-9-2017
CAMHS/Lodge Road TAJ51
Sample Record Number: FU000414
Basement -1, Plant Room 007-03-(-1)-001 Position Location :Floor
Inspection Date
14/9/2016
Component:
Dust Debris
Sample No.
FU000414
Survey Type
Type 2
Surveyor
Richard Farmer
Asbestos type
Chrysotile
Quantity of Material
15m²
Material Assessment Material
3 Extent of Damage
3
Surface Treatment
2 Asbestos Type
1
Material Assessment Total:
9 B
Comments: Restrict access and remove material as soon as
possible.
Priority Assessment Main Type of Activity
0 Extent of Material
2
Maintenance Activity
0 Location
2
Accessibility
0 Number of Occupants
0
Frequency of use
0 Average time is in use
0
Frequency of maintenance activity
1
Risk Assessment Total:
2
Total Score:
11 Slight Risk
Actions Arising
Due Date
Est. Cost
Remove under Controlled Conditions by Approved
Contractor.
9-11-2016
£0
Re-Inspection Schedule:
Status
Due Date
Due after six Months
14-9-2017
CAMHS/Lodge Road TAJ51
Sample Record Number: FU000415
Basement -1, Plant Room 007-03-(-1)-001 Position Location :Ceiling
Inspection Date
14/9/2016
Component:
Residue
Sample No.
FU000415
Survey Type
Type 2
Surveyor
Richard Farmer
Asbestos type
Chrysotile
Quantity of Material
1m²
Material Assessment Material
3 Extent of Damage
3
Surface Treatment
2 Asbestos Type
1
Material Assessment Total:
9 B
Comments: Restrict access and remove material as soon as
possible.
Priority Assessment Main Type of Activity
0 Extent of Material
1
Maintenance Activity
0 Location
2
Accessibility
0 Number of Occupants
0
Frequency of use
0 Average time is in use
0
Frequency of maintenance activity
1
Risk Assessment Total:
2
Total Score:
11 Slight Risk
Actions Arising
Due Date
Est. Cost
Remove under Controlled Conditions by Approved
Contractor.
9-11-2016
£0
Re-Inspection Schedule:
Status
Due Date
Due after six Months
14-9-2017
Bulk Analysis Report
Client: Sandwell New Code Address: CAMHS/Lodge Road TAJ51 Date: 08/12/2016
Survey Report Number J099844
Sample Ref. Sample Location
Sample Description
Asbestos Types
No.
J054909PS69 CAMHS/Lodge Road TAJ51
Gaskets
Chrysotile
FU000410
Plant Room 007-03-(-1)-001 Flash Guard
Chrysotile
FU000411
Plant Room 007-03-(-1)-001 Residue
Chrysotile
FU000412
Plant Room 007-03-(-1)-001 Residue
Chrysotile
FU000413
Plant Room 007-03-(-1)-001 Residue
Chrysotile
FU000414
Plant Room 007-03-(-1)-001 Dust Debris
Chrysotile
FU000415
Plant Room 007-03-(-1)-001 Residue
Chrysotile
Sample analysis was conducted in accordance with in house procedures and the methodology
contained in MDSHS77 (Asbestos in bulk materials. Sampling and identification by polarised light
microscopy. June 1994). The information provided concerning sample locations is as provided by the
client no liability can be accepted for the accuracy of this information Comments, Opinions,
Recommendations are outside the scope of our UKAS accreditation. Determination of concentration is
outside the scope of laboratory accreditaion
Key = Chysotile: White Asbetsos Amosite: Brown Asbestos Crocidolite: Blue Asbestos NAD: No
Asbestos Detected
Areas With No Suspect Materials
Within the Definition of this type of Survey
CAMHS/Lodge Road
TAJ51
Basement
-1
Ground Floor
00
Entrance
007-03-00-001
Waiting Area
007-03-00-002
Consult/Exam Room
007-03-00-003
Circulation – Lobby
007-03-00-004
Office
007-03-00-005
Circulation – Corridor
007-03-00-006
Consult/Exam Room
007-03-00-007
Kitchenette
007-03-00-008
Sluice
007-03-00-009
W.C. – Assisted
007-03-00-010
W.C.
007-03-00-011
W.C.
007-03-00-012
Consult/Exam Room
007-03-00-013
Circulation – Corridor
007-03-00-014
Circulation – Lift
007-03-00-015
Circulation – Corridor
007-03-00-017
Store – Medical Records
007-03-00-018
Consult/Exam Room
007-03-00-019
Store – Cleaners
007-03-00-020
Server Room
007-03-00-021
First Floor
01
Circulation – Lobby
007-03-01-001
Consult/Exam Room
007-03-01-002
Consult/Exam Room
007-03-01-003
Consult/Exam Room
007-03-01-004
Consult/Exam Room
007-03-01-005
Consult/Exam Room
007-03-01-006
CAMHS/Lodge Road
TAJ51
First Floor
01
Office
007-03-01-007
Consult/Exam Room
007-03-01-008
Consult/Exam Room
007-03-01-009
Consult/Exam Room
007-03-01-010
Consult/Exam Room
007-03-01-011
Consult/Exam Room
007-03-01-012
Consult/Exam Room
007-03-01-013
Circulation – Lobby
007-03-01-014
W.C.
007-03-01-015
Kitchenette
007-03-01-016
Group Room
007-03-01-017
Circulation – Lobby
007-03-01-018
W.C.
007-03-01-019
W.C.
007-03-01-020
Consult/Exam Room
007-03-01-021
Consult/Exam Room
007-03-01-022
Circulation – Stairs
007-03-01-023
Circulation – Corridor
007-03-01-024
Circulation – Corridor
007-03-01-025
Circulation – Lift
007-03-01-026
Circulation – Corridor
007-03-01-027
Group Room
007-03-01-028
Circulation – Corridor
007-03-01-029
Second Floor
02
Staff Room
007-03-02-001
W.C.
007-03-02-002
W.C.
007-03-02-003
W.C.
007-03-02-004
W.C.
007-03-02-005
Office
007-03-02-006
CAMHS/Lodge Road
TAJ51
Second Floor
02
Office
007-03-02-007
Office
007-03-02-008
Office
007-03-02-009
Office
007-03-02-011
Office
007-03-02-012
Office
007-03-02-013
Quiet Room
007-03-02-014
Quiet Room
007-03-02-015
Circulation – Stairs
007-03-02-016
Circulation – Corridor
007-03-02-017
Circulation – Corridor
007-03-02-018
Circulation – Corridor
007-03-02-019
Circulation – Lobby
007-03-02-020
Circulation – Lift
007-03-02-021
Staff Room
007-03-02-022
Asbestos Re-Inspection Schedule
Date: 8/12/2016
Survey Report Number J099844
In Chronological Order
Due after six Months
Sample Location
Description Comments
Due Date
Status
CAMHS/Lodge Road Gaskets
14/9/2017 Due after six
Months
CAMHS/Lodge
Flash Guard
14/9/2017 Due after six
Road,Basement,Plant
Months
Room,007-03-(-1)-
001
CAMHS/Lodge
Residue
14/9/2017 Due after six
Road,Basement,Plant
Months
Room,007-03-(-1)-
001
CAMHS/Lodge
Residue
14/9/2017 Due after six
Road,Basement,Plant
Months
Room,007-03-(-1)-
001
CAMHS/Lodge
Residue
14/9/2017 Due after six
Road,Basement,Plant
Months
Room,007-03-(-1)-
001
CAMHS/Lodge
Dust Debris
14/9/2017 Due after six
Road,Basement,Plant
Months
Room,007-03-(-1)-
001
CAMHS/Lodge
Residue
14/9/2017 Due after six
Road,Basement,Plant
Months
Room,007-03-(-1)-
001
No Historical Events Pending