Statement from Amanda Robinson, regarding acoustic checks undertaken on the 12th and 18th June 2004 
 
 
Further to our site visit undertaken this morning to repeat the measurements of the west wing chillers following 
works carried out by Powermaster, we provide the following summation. 
 
1.  Without the chillers operating, the noise levels within the office area on the fourth floor adjacent to the 
plantroom were of the order of NR35 in their current condition (this noise is likely to reduce further once 
carpets are installed). When the chillers were first turned on, the noise levels in the 4th floor office area 
increased to NR 46, and the tonal noise noted previously (250Hz) was clearly audible. However, after the 
chillers had operated for a period of time, the noise levels reduced to between NR40 – 45. 
 
2.  The chillers were turned off again, and the settings adjusted by Derry’s. The measurements were repeated, 
and it was found that this time, the noise levels with all plant operating were NR36 – NR41.  
 
3.  It would appear that the chiller noise level varies upon its initial start-up, as it adjusts to accommodate the 
load. However, once operating under the required conditions, the noise produced reduces, and the tonal 
content at 250Hz is significantly reduced. Following the works carried out by Powermaster, there has clearly 
been a significant reduction in the noise level associated with the operation of the chillers. However, it should 
be ensured that the specific condition that is creating the noise on startup is suitably controlled. 
 
4.  On the basis of the measurements taken on the second startup of the chillers, the noise on the fourth floor 
adjacent the plant areas achieves the internal noise requirement of NR38 within the space.  
 
5.  It was noted upon inspection of the plantroom areas that there are still gaps around elements such as beams, 
pipework and at the head of the partition etc., which are required to be sealed airtight. It is understood from 
your discussions at the meeting this morning that B&K have committed to undertaking this task. 
 
 
 
 
 
 
Page: 1 
Doc. 29B 
 
 
 
C:\Documents and Settings\david.tinsley.DERRY-BS\Local Settings\Temporary Internet Files\OLK679\Chiller Acoustic Resultst_ar180604_memo on chiller repeat measures.doc 
 
 

 
Building 
Description 
Comment 
31.5 Hz  63 Hz  125 Hz 250 Hz 500 Hz 1.0 k 
2.0 k 
4.0 k 
8.0 k 
NR 
Leq 
East Wing 
4th floor near plantroom 
water noise from pipework 
58.9 
54.5 
51.3 
48.5 
40.8 
37 
30.8 
25.7 
20.7 
39 
44.1 
 
4th floor near plantroom 
water noise from pipework 
61.6 
53.2 
53.1 
48.4 
41 
38.8 
32.7 
27.9 
25.8 
39 
44.9 
 
4th floor near door to atrium 
 
54.5 
49.1 
45.7 
41.9 
36.6 
36.9 
34.4 
25.2 
18.5 
37 
41.5 
 
4th floor near plant area south side 
water noise prevalent 
57.4 
53.4 
49.3 
45.2 
42 
42.4 
39.7 
31.6 
22.6 
43 
46.6 
 
4th floor as above without water noise 
pumps off, therefore no water noise 
57.8 
52.2 
49.2 
44.9 
38.5 
32.8 
27.1 
21.3 
14.3 
35 
40.8 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
East Wing chillers  in-between chillers, 2 compressors and 2 sets of fans 
no specific tonal noise 
69.1 
67.9 
68.3 
71.2 
70.7 
67 
59.2 51.2 41.1 68 71.3 
 
underneath chillers on 3rd floor 
cannot hear chillers 
61.4 
54.5 
50.1 
42.4 
36 
29.3 
24.7 
20.7 
17.2 
33 
39 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
West Wing 
street area 3rd floor 
 
59.7 
56.2 
51.8 
49.1 
44.6 
39.8 
34.5 
32.2 
27 
41 
46.3 
 
3rd floor central area 
water noise present 
60.5 
57.1 
52 
45.6 
38.8 
39.7 
37.3 
31.2 
24.7 
40 
44.9 
 
3rd floor central area 
pumps off, therefore no water noise 
60.2 
57.2 
52.3 
45.7 
38.7 
32.8 
25.5 
20.2 
18.1 
36 
41.7 
 
3rd floor near door on south side 
pumps off, therefore no water noise 
60.2 
55.5 
49.7 
43.3 
36.7 
28.7 
23 
19.9 
15.9 
34 
39.3 
 
2nd 
floor 
general 
 
61.4  55.2 51.5  45  37.4 30.9 25.1 21.1 18.7  35  40.7 
 
2nd floor under noisy FCU 
sounds like fcu rattling 
61.5 
57.1 
54 
49.3 
40.7 
35.4 
24.3 
19.2 
15.1 
40 
44.1 
 
ground 
floor 
near 
door 
 
60.8  57.7 53.9 48.6 40.1 34.4 27.1 24.2 18.5  39  43.7 
 
ground floor at edge of street 
 
60.9 
57.4 
52.3 
46.7 
39.1 
32.5 
27.3 
25 
20.2 
37 
42.3 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
West Wing chillers 4th floor near plantroom 
chiller noise dominant (tonal 250/500Hz)
65.6 
52.5 
53.4 
57.1 
39.9 
35 
28.4 
21.3 
17.7 
49 49 
 
underneath chillers on 3rd floor 
chiller noise dominant (tonal 250/500Hz)
63.6 
58.3 
54.5 
50.3 
43 
36.6 
30.9 
28.5 
24.2 
41 
45.8 
 
west wing 4th floor near plantroom 
one chiller only running, tone eliminated 
66.9 
52.9 
50.4 
47.3 
39.3 
34.8 
29.3 
27.8 
22.1 
38 
42.7 
 
around 1m from chillers, both on 
subjectively chiller closer to office noisier
73 
72.6 
71.3 
80.6 
78.8 
76.5 
67.9 
60.4 
52.1 
77 
80.2 
 
around 1m from chiller, one on only 
one chiller only 
70.6 
69 
64.7 
69.9 
67.9 
67.3 
55.6 
48 
44.8 
67 
70 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Measurements as taken on the 12 June 2004 
 
 
 
Page: 2 
Doc. 29B 
 
 
 
C:\Documents and Settings\david.tinsley.DERRY-BS\Local Settings\Temporary Internet Files\OLK679\Chiller Acoustic Resultst_ar180604_memo on chiller repeat measures.doc 
 
 

 
Building 
Description 
Comment 
31.5 Hz 63 Hz  125 Hz 250 Hz 500 Hz 1.0 k 
2.0 k 
4.0 k 
8.0 k 
NR 
Leq 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
West 
Wing 
chillers 
4th 
floor 
near 
plantroom 
no 
chiller, 
pumps 
etc. 
only 
51.9  53.8 52.5 44.1 36.7 34.1 30.5 25.3 20.6 35.1 41.8 
 
 
4th floor near plantroom, chillers on  tonal noise at 250Hz dominant 
53.7 
56.2 
53.4 
54.8 
39 
36.8 
31.9 
26.5 
21 
46 
47.5 
 
4th floor near plantroom, chillers on  tonal noise at 250Hz dominant 
60.3 
60.8 
58.7 
52.8 
38.9 
37.8 
32.1 
21.8 
15.4 
43.9 
47.4 
 
in-between chillers, both on 
Subjectively much better than on previous inspection 
67.3 
70.7 
70.6 
73 
74.3 
72.1 
63.1 
52.5 
44.2 
72.1 75.4 
 
 
 
 
 
 
 
 
 
 
 
 
 
no chiller, pumps etc. only 
no chiller, pumps etc. only 
54.2 
53.7 
52.9 
45.3 
36.3 
33.8 
29.3 
26.1 
28.7 
35.8 
42.2 
Chiller turned off, 
tonal noise from chiller at 250Hz audible, but not as high as 
then back on again  4th floor near plantroom 
previously 
53.1  51.4 52.6 50.3 36.7 33.3 28.3 18.5 14.1 41.2 43.9 
 
4th floor near plantroom 
tonal noise from chiller barely audible 
53.5 
54.2 
53.1 
44.5 
37.5 
35.7 
30.9 
20.8 
15.1 
35.7 
42.4 
 
Measurements as taken on the 18 June 2004