Salix Homes – Fire Risk Assessment Report for Riverbank Tower, Salford, M3 7JY 
 
 
 
 
 
 
Contents 
 
 

 
 
 
1.0 
Introduction ................................................................................................ 3 
 
2.0 
Background................................................................................................ 5 
 
3.0 
The Inspection ........................................................................................... 7 
 
4.0 
The Report ................................................................................................. 8 
 
5.0  
Elemental Summary................................................................................... 9 
 
6.0  
Main Summary......................................................................................... 13 
 
 
 
 
 
Appendix 1…………………………………………………………………...Scott Schedule 
 
 
 
 
 
 
Pennington Choices Limited – 29 Jul 09 

Our reference: SLX878 
Prepared by – TM 
 
Checked by - GB 
 
Printed on 100% recycled paper 

                                                                                                                         
Salix Homes – Fire Risk Assessment Report for Riverbank Tower, Salford, M3 7JY 
 
 
 
 
 
 
1.0 
Introduction 
 
1.1 
The Client 
 
Salix Homes. 
 
1.2  
The Property 
 
The property is Riverbank Tower, Salford, M3 7JY. 
 
1.3 
Date of Inspection 
 
The property was inspected on 11th December 2008. 
 
1.4 
Brief Description 
 
The property comprises a 16 storey block of flats. The property is understood 
to  have  been  built  c1970,  and  comprises  92  purpose-built  residential  flats, 
with 6 flats per floor.  
 
The  property  appeared  to  be  of  reinforced  concrete  modular  construction, 
with two lift shafts, and a single accommodation/Means of Escape staircase. 
Each floor  is  logically  laid  out,  with  a  corridor  around  a central  core  housing 
the staircase, lifts, refuse chute, and service risers. The corridor on each floor 
is lobbied, each side serving three flats.  
 
The property provides residential accommodation. 
 
1.5 
Proposal 
 
A  proposal  letter  dated  21  October  2008  was  submitted  to  Salix  Homes 
offering surveying services.  
 
1.6 
Limitations 
 
The Report is for the sole use of the named Client and is confidential to the 
Client and their professional advisors.  Consequently, no responsibility can be 
accepted to any other party in respect of its contents in whole or in part and 
the  Contracts  (Rights  of  Third  Parties)  Act  1999  shall not  apply.    Before  the 
Report or any part is reproduced or referred to in any document, our written 
approval as to the form and content must be obtained. 
 
The  assessment  does  not  provide  any  indication  of  the  condition  of  the 
building  or  its  elements,  fixtures  or  fittings,  and  is  not  for  any  statutory 
purpose. 
 
 
Pennington Choices Limited – 29 Jul 09 

Our reference: SLX878 
Prepared by – TM 
 
Checked by - GB 
 
Printed on 100% recycled paper 

                                                                                                                         
Salix Homes – Fire Risk Assessment Report for Riverbank Tower, Salford, M3 7JY 
 
 
 
 
 
 
The  report  summary  provides  an  overview  of  the  appended  Fire  Risk 
Assessment  Schedule,  highlighting  significant  and  recurrent  issues.  Any 
generalisations  made  within  the  summary  have  been  made  by  the  surveyor 
using their judgement and based on the information recorded in the Fire Risk 
Assessment report. 
 
The appended Schedule takes a general approach, recording the information 
deemed  appropriate  or  relevant  at  the  time  of  the  inspection,  following 
structured prompts. Where there may be a subjective judgement required, the 
surveyor  has  made  this  using  their  professional  opinion  based  on  the 
circumstances at the time of the inspection. 
 
1.7 
Fees and Expenses 
 
The Client will pay Pennington Choices Limited the agreed fee for the Report 
inclusive of VAT and disbursements. 
 
1.8 
Complaints 
 
The Company has a full complaints procedure and in the unlikely event of a 
complaint arising,  please  contact the  author  regardless  of  the  issue  who  will 
be pleased to assist.  If however, you cannot resolve the issue in this manner, 
please write to Mr Mark Seaborn, Managing Director. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Pennington Choices Limited – 29 Jul 09 

Our reference: SLX878 
Prepared by – TM 
 
Checked by - GB 
 
Printed on 100% recycled paper 

                                                                                                                         
Salix Homes – Fire Risk Assessment Report for Riverbank Tower, Salford, M3 7JY 
 
 
 
 
 
 
2.0 
Background 
 
The Fire Precautions (Workplace) Regulations 1997, as amended by the Fire 
Precautions (Workplace) (Amendment) Regulations 1999.  
 
 
The regulations are designed to provide for a minimum fire safety standard in 
places  where  people  work,  including  shared  areas,  workplace  facilities,  and 
the means of access to that workplace. This has been achieved by amending 
‘The  Management  of  Health  and  Safety  at  Work  Regulations  1992’  which 
requires  all  employers  to  conduct  a  risk  assessment  regarding  health  and 
safety matters and if you employ more than five persons it has to be a written 
assessment.  The  1997  regulations  now  require  you  to  consider  the  Fire 
Safety  aspect  (i.e.  Part  II  of  the  1997  regulations)  as  part  of  the  risk 
assessment or as an addition to it.  
 
 
In  December  1999  the  Fire  Precautions  (Workplace)  (Amendments) 
Regulations  1999  came  into  force.  These  amendments  brought  larger 
employers,  (those  requiring  a  Fire  Certificate),  within  the  scope  of  these 
regulations  and  subsequently  requiring  them  to  carry  out  a  fire  risk 
assessment.  
 
 
In 2005 the Regulatory Reform (Fire Safety) Order 2005 came into force.  
 
 
 
The  Order covers  general fire  precautions  and  other fire  safety  duties  which 
are  needed  to  protect  ‘relevant  persons’  in  case  of  fire  in  and  around  most 
‘premises’.  The  Order  replaces  previous  fire  safety  legislation.  Any  fire 
certificate  issued  under  the  Fire  Precautions  Act  1971  ceased  to  have  any 
effect.  You  must  carry  out  a  fire  risk  assessment  and  keep  it  up  to  date  to 
ensure  that  all  the  fire  precautions  in  your  premises  remain  current  and 
adequate.  
 
 
If  a  Fire  Risk  Assessment  had  been  carried  out  under  the  Fire  Precautions 
(Workplace)  Regulations  1997, as  amended  1999,  and this  assessment has 
been  regularly  reviewed,  this  should  be  revised  the  fire  risk  assessment 
taking  into  account  the  wider  scope  of  the  Regulatory  Reform  (Fire  Safety) 
Order 2005. 
 
2.1 
Responsibility for Enforcement of the Fire Safety Order  
 
  
Local  fire  and  rescue  authorities  (the  fire  and  rescue  service)  have 
responsibility  for  the  supervision  and  enforcement  of  the  regulations.  It  is, 
however,  the  employer’s  duty  to  identify  and  take  appropriate  measures  to 
comply  with  the  Regulations.  In  our  opinion,  Salix  Homes  have  a 
responsibility to comply with the Order. 
  
The  Fire  Safety  Order  requires  employers  to  carry  out  a  Fire  Risk 
Assessment to: 
 
• 
Identify the fire hazards. 
 
Pennington Choices Limited – 29 Jul 09 

Our reference: SLX878 
Prepared by – TM 
 
Checked by - GB 
 
Printed on 100% recycled paper 

                                                                                                                         
Salix Homes – Fire Risk Assessment Report for Riverbank Tower, Salford, M3 7JY 
 
 
 
 
 
 
• 
Reduce  the  risk  of  those  hazards  causing  harm  to  as  low  as  is 
reasonably practicable. 
• 
To  decide  what  physical  fire  precautions  and  management 
arrangements  are  necessary  to  ensure  the  safety  of  people  in  your 
premises if a fire does start. 
• 
Provide  and  maintain:  means  for  detecting  fire;  Means  of  Escape; 
emergency lighting; fire safety signs; and fire fighting equipment.  
• 
Monitor and review the risk assessment.  
• 
Inform staff including providing training.  
• 
Plan for an emergency.  
• 
Nominate persons to assist. 
  
  
Failure  to  comply  with  the  Regulations,  resulting  in  one  or  more  persons 
being placed at serious risk is a criminal offence in itself and in these cases 
the  fire  and  rescue  authority  may  consider  immediate  enforcement  action 
and/or secure prosecution of the offence via the court. 
 
 
Pennington Choices Limited – 29 Jul 09 

Our reference: SLX878 
Prepared by – TM 
 
Checked by - GB 
 
Printed on 100% recycled paper 

                                                                                                                         
Salix Homes – Fire Risk Assessment Report for Riverbank Tower, Salford, M3 7JY 
 
 
 
 
 
 
3.0 
The Inspection 
 
3.1 
Inspection 
 
 
  
The  aim  is  to follow  a  normal  and  logical  approach,  entry and  route  through 
the  building  and  make  a  visual  assessment  of  the  premises  with  regard  to 
adequacy of fire safety.  
 
3.2 
Limitations  
 
  
The  inspection  will  be  restricted  to  those  communal  areas  agreed  with  the 
Client  and  specified  in the  brief.  The  inspection  specifically  excludes  private 
flats  or  dwellings  or  premises  outside  the  communal  areas  within  the 
responsibility of the Client. 
 
3.3 
Recording  
 
  
The Fire Risk Assessment is undertaken with a checklist that has been drawn 
up  to  reflect  fire  safety  measures  as  described  by  ‘Fire  Safety  Risk 
Assessment– Sleeping Accommodation’ published by HM Government. 
  
3.4 
Consultation  
 
  
The  Block  Superintendent  for  the  premises  was  consulted  briefly  over  fire 
safety issues relating to the premises. 
 
 
Pennington Choices Limited – 29 Jul 09 

Our reference: SLX878 
Prepared by – TM 
 
Checked by - GB 
 
Printed on 100% recycled paper 

                                                                                                                         
Salix Homes – Fire Risk Assessment Report for Riverbank Tower, Salford, M3 7JY 
 
 
 
 
 
 
4.0 
The Report  
 
4.1 
Reporting  
 
  
Unless  agreed  otherwise  at  the  time  of  instruction,  comments  are  to  assist 
you to meet your duties under the Fire Precautions (Workplace) Regulations 
1997  as  amended  by  the  Fire  Precautions  (Workplace)(Amendment) 
Regulations 1999.  
 
4.2 
Costs  
 
   
The Report does not include any detailed costing or estimates, and for these  
reasons any advice on the cost or scope given will be based on ‘spot prices’ 
only  for  guidance  and  would  exclude  allowances  for  Preliminaries, 
Contingency Sums, professional fees and VAT.  
 
4.3 
Action  
 
  
Each  item  has  been  given  a  priority  weighting  to  categorise  and  assist 
scheduling improvement work. Our definitions are as follows:  
 

Immediate  -  Urgent  action  required  to  reduce  or  eliminate  serious 
threats  to  Fire  Safety.  Failure  to  act  may  contravene  statutory 
requirements  and  could  lead  to  the  issue  of  notices  of  legal 
proceedings by the Enforcing Authority.  
 
B  
Improvement  Required  -  Short  to  medium  term  action  required. 
Planned  Action  required  to  reduce,  or  remove  lesser  but  real  threats 
to Fire Safety. Contravention may lead to the issue of Notices, legal  
proceedings or a letter by the Enforcing Authority.  
 
C  
Improvement  Required  -  Plan  as  part  of  a  program  of  similar  work, 
repair or renewal. Action desirable to demonstrate that precautions or 
techniques are consistent with good Fire Safety controls and practice.  
Serious harm unlikely. 
  
D  
Management - An issue of policy or procedure to be addressed by  
 
 
Management. 
 
 
Pennington Choices Limited – 29 Jul 09 

Our reference: SLX878 
Prepared by – TM 
 
Checked by - GB 
 
Printed on 100% recycled paper 

                                                                                                                         
Salix Homes – Fire Risk Assessment Report for Riverbank Tower, Salford, M3 7JY 
 
 
 
 
 
 
5.0  
Elemental Summary  
 
5.1 
Fire Hazards  
 
  
The main sources of ignition in the building are the electrical switchgear, and 
lift  motor  room  equipment.  Where  possible,  sources  of  ignition  should  be 
removed from the building. If this is not possible, management controls must 
be  put  in  place  to  restrict  unauthorised  access,  remove  contact  with 
combustible  materials,  improve  warning  capabilities,  and  provide  regular 
maintenance. 
 
  
Flats  within  the  building  are  understood  to  have  gas  central  heating,  with 
each  flat  having  a  central  heating  boiler.  Residents  who  have  gas  fired 
appliances  should  provide  evidence  of  regular  servicing  by  a  CORGI 
registered gas engineer. 
 
  
Stored  items  and  furniture  in  communal  areas  can  be  a  source  of  fuel  and 
can obstruct the Means of Escape, in case of emergency. A sofa was noted 
in  a  lobby  on  the  8th  floor.  This  must  be  removed.  The  Building 
Superintendent  was  advised  of  this,  at  the  time  of  the  inspection.  It  is 
understood  that  the  Block  Superintendent  undertakes  daily  inspections  to 
check that all communal areas and escape routes are kept clear.  
 
  
Bin stores are locations which are at potential risk from arson. Bin stores and 
other plant rooms must be maintained locked.   
 
5.2 
People who are at significant risk from fire 
 
  
There  is  understood  to  be  a  ‘Stay-put’  fire  policy  for  occupants  of  flats, 
whereby the degree of fire compartmentation is such that any potential fire is 
likely  to  be  contained.  See  also  the  points  under  the  Heading  ‘Means  of 
Escape’.  
  
5.3 
Structural Features  
  
The  building  construction  comprises  non-combustible  construction,  i.e. 
elements  of  structure;  floors,  walls  and  staircases,  comprise  supporting 
structure  of  brick  or  concrete.  The  construction  of  the  escape  routes  should 
prevent the fabric of the building from being involved in the spread of any fire 
which may occur. 
5.4 
Monitoring during maintenance and refurbishment 
 
   
Sources of heat or combustible materials may be introduced into the building 
during  periods  of  maintenance  or  refurbishment.  Where  maintenance  or 
refurbishment  involves  ‘hot  works’,  careful  control  is  necessary.  Method 
statements  for  safe  working  should  be  requested  from  the  contractor  and 
approved  prior  to  commencement,  and  a  Permit  to  Work  system  should  be 
put  in  place.  Furthermore,  all  materials  brought  onto  the  site  in  connection 
 
Pennington Choices Limited – 29 Jul 09 

Our reference: SLX878 
Prepared by – TM 
 
Checked by - GB 
 
Printed on 100% recycled paper 

                                                                                                                         
Salix Homes – Fire Risk Assessment Report for Riverbank Tower, Salford, M3 7JY 
 
 
 
 
 
 
with  the  works  should  be  stored  away  from  sources  of  heat  and  must  not 
obstruct exit routes. 
 
As part of the Permit to Work system, contractors visiting the building should 
be logged in and out, to ensure that security staff are alert to their presence in 
the  building  in  an  emergency,  when  a  contractor  may  be  working  in  remote 
plant areas. 
  
5.5 
Fire Detection and Warning  
 
   
The degree of fire compartmentation and the non-combustible construction is 
such  that  the  installation  of  fire  alarms  in  communal  areas  is  not  required 
under the guidance given in HM Government ‘Fire Safety Risk Assessment – 
Sleeping  Accommodation’,  providing  that  other  risk  management  measures 
are in place. It is therefore recommended that independent smoke detectors 
are  installed  in  each  flat.  This  is  in  order  that  occupants  can  be  alerted  to  a 
potential fire within their accommodation. 
 
5.6 
Means of Escape  
 
  
There is understood to be a  ‘Stay-put’ policy for occupants of flats, whereby 
the degree of fire compartmentation is such that any potential fire is likely to 
be contained. Evacuation from a flat in which a fire occurs, into the communal 
corridors,  as  a  place  of  safety,  is  deemed  to  be  acceptable  under  the 
guidance given in HM Government ‘Fire Safety Risk Assessment – Sleeping 
Accommodation’. It is, however, important that no flammable items are stored 
in the communal corridor or staircase areas. 
 
The  primary  Means  of  Escape  is  the  single  staircase,  which  is  accessed 
directly  off  the  lift  lobby  on  each  floor.  The  lift  lobby  doors  to  the 
accommodation  corridors  appeared  to  have  been  upgraded  to  half  hour  fire 
resistance.  
 
At  ground  floor  level,  the  door  from  the  staircase  into  the  lift  lobby  opens 
across  the  landing  at  the  bottom  of  the  staircase.  This  could  cause 
entrapment.  The  door  must  be  re-hung  to  open  outwards  into  the  lift  lobby, 
and in the direction of the Means of Escape.  
 
The alternative Means of Escape from the entrance reception is through the 
secondary entrance. The width of the corridor is acceptable. 
 
  
The  staircase  nosings  are  painted  the  same  colour  as  the  treads  and  risers 
and are not therefore readily identifiable. It is important that these are clearly 
visible,  particularly  in  low  light  conditions  in  an  emergency.  Fluorescent 
nosings should be installed. 
 
  
 
 
Pennington Choices Limited – 29 Jul 09 
10 
Our reference: SLX878 
Prepared by – TM 
 
Checked by - GB 
 
Printed on 100% recycled paper 

                                                                                                                         
Salix Homes – Fire Risk Assessment Report for Riverbank Tower, Salford, M3 7JY 
 
 
 
 
 
 
5.7 
Doors  
 
   
The  final  exit  doors  and  internal  lobby  door  are  currently  secured  by 
electromagnetic locks, with remote door releases. The doors are not provided 
with  manual  ‘break  glass’  units.  Green  break  glass  units  should  be  installed 
for these doors to allow the doors to be manually released, in an emergency.  
 
  
The refuse chute is accessed in lobbies off the main lift lobbies on each floor. 
Refuse  chutes  constitute  potential  means  of  transmission  of  fire  and  smoke 
up  the  building.  The  lobby  doors  currently  are  not  fire  resisting  doors,  and 
should be upgraded to a minimum half hour fire resistance. 
 
5.8 
Lighting  
 
   
The  lighting  of  communal  areas  within  the  building  includes  emergency 
lighting. Emergency lighting must be maintained and tested regularly at least 
every six months. 
 
5.9 
Signs  
 
   
The current signage to the building does not meet the relevant requirements 
of the Health and Safety (Safety Signs and Signals) Regulations 1996.  
 
  
Exit signs on doors, or indicating exit routes, should be provided and should 
be in a position where they can be clearly seen. The signs must take the form 
of  a  pictogram,  which  may  incorporate  a  directional  arrow.  Signs  on  exit 
routes  should  have  directional  arrows,  ‘up’  for  straight  on  and  ‘left,  right,  or 
down’ according to the route to be taken. Advice on specific fire signage can 
be found in ‘Fire Safety Signs’. 
 
  
There were no Fire Action signs providing instructions for actions in the event 
of  an  emergency.  Fire  Action  signage  should  be  installed  on  each  floor 
landing. 
 
5.10 
Fire-fighting Equipment  
 
   
The  building  is  provided  with  a  dry  riser  installation  for  use  by  the  Fire  and 
Rescue Service. It is understood that this is inspected and pressure tested by 
the Fire and Rescue Service on an annual basis. 
 
5.11 
Training and Instructions  
 
  
Escape  routes  should  be  inspected  regularly  as  part  of  the  maintenance 
policy to ensure that these are kept clear.  
 
 
All  existing  residents  should  be  updated  on  any  changes  to  emergency 
procedures.  New  residents  should  receive  a  briefing  on  emergency 
procedures and this should be documented in their induction pack. 
 
 
Pennington Choices Limited – 29 Jul 09 
11 
Our reference: SLX878 
Prepared by – TM 
 
Checked by - GB 
 
Printed on 100% recycled paper 

                                                                                                                         
Salix Homes – Fire Risk Assessment Report for Riverbank Tower, Salford, M3 7JY 
 
 
 
 
 
 
5.12 
Maintenance and Testing of Fire Safety Equipment  
 
   
To  safeguard  the  occupants,  all  equipment  and  devices  provided  as  part  of 
the  Fire  Safety  Plan  should  be  the  subject  of  a  suitable  system  of 
maintenance.  
 
Written  records  are  to  be  kept  of  all  actions  taken  in  case  evidence  is 
required at a possible future inquiry or legal action.  
 
5.13 
Emergency Plan  
 
An  Emergency  Plan  should  be  in  place  to  carry  forward  information  and 
recommendations  from  the  Fire  Risk  Assessment.  The  aim  of  the  plan  is  to 
ensure  that  in  the  event  of  a  fire  everyone,  including  employees,  residents, 
visitors  and  contractors  etc.  are  sufficiently  familiar  with  the  action  they 
should take, and can be safely evacuated to a location out of danger. 
 
 
 
Pennington Choices Limited – 29 Jul 09 
12 
Our reference: SLX878 
Prepared by – TM 
 
Checked by - GB 
 
Printed on 100% recycled paper 

                                                                                                                         
Salix Homes – Fire Risk Assessment Report for Riverbank Tower, Salford, M3 7JY 
 
 
 
 
 
 
6.0  
Main Summary  
 
  
The building does not currently comply with the Regulations specified above 
and  hence  there  are  urgent  works  required  to  remedy  this  situation.  Such 
works include: 
 
• 
Upgrading of the fire resistance of the doors to the refuse chute lobbies. 
• 
Installation  of  independent  smoke  detectors  in  the  flats,  if  not  already 
installed. 
• 
Re-hanging  of  the  door  at  the  foot  of  the  staircase,  to  open  outwards 
into the lift lobby. 
• 
Removal  of  redundant  furniture  from  8th  floor  lobby,  and  keeping  all 
communal areas clear, at all times. 
• 
Installation  of  green  manual  ‘break  glass’  units  for  the  final  exit  doors 
and the reception lobby door. 
• 
Improvement of fire signage. 
  
  
We would recommend the implementation of work following the prioritisation 
categories listing within the attached Scott Schedule.  
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
  
 
 
 
 
 
Pennington Choices Limited – 29 Jul 09 
13 
Our reference: SLX878 
Prepared by – TM 
 
Checked by - GB 
 
Printed on 100% recycled paper 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Appendix 1 
 
Scott Schedule